SNR RDC-48-540-STD [8/15] Ix environmental testing requirements

SNR RDC-48-540-STD [8/15] Ix environmental testing requirements
Page 8 of 15
Battery management: No influence for backup battery management without monitoring module when rear
battery is 7AH or 12AH. When rear battery is between 1730A, supervisory sends order to set battery
arrangement, at then charging battery current limiting is 3A.
3. Interface
There is a three-core AC input socket for power supply input which are integrated in the rear panel. There
are two DC output interfaces, one backup battery interface, monitoring interface RS232.
IX. Environmental Testing Requirements
Items Requirements Results
High temperature
operation
65℃,24Hrs .Tested firstly under high temperature of 65 &
normal atmosphere pressure for 16hrs; then for 4hurs under high
temperature low atmosphere pressure and 4hrs under high
temperature high atmosphere pressure and rapidly switch on/off less
than 5 times.
Power module works
normally, power
on/down normally.
Low temperature
operation
-25℃,24Hrs. Tested firstly under low temperature of -25 &
normal atmosphere pressure for 16hrs; then for 4hurs under low
temperature & low atmosphere pressure and 4hrs under low
temperature & high atmosphere pressure and rapidly switch on/off
less than 5 times.
Power module works
normally, power
on/down normally.
High Temperature
Storage
Stored under 70 for 24hrs, and recover for 2hrs under
room temperature
Power module works
normally
Los temperature
Storage
Stored under -40 for 24hrs, and recover for 2hrs under
room temperature
Power module works
normally
High/low
temperature
variation
-2565 ℃,5 /min under limit temperature for each 2hrs and
vary temperature for 2 circles
Power module works
normally
Random vibration: sample can endure 5-500Hz random vibration at 3
axis for 20 minutes each, acceleration spectral density of 510Hz is
13 m
2
/s
3
10200Hz is 3m
2
/s
3
200500Hz is 1m
2
/s
3
.
Power module works
normally after test.
Vibration
Operation vibration: 3 axis for 90 minutes each under frequency
range of 5-100-5Hz with acceleration of 0.1g and scan frequency of
0.1oct/min.
Power module works
normally during testing.
Shock
Shock wave shape: Half sine wave at 3 axis for ±3 times each with
peak value acceleration of 300m/S
2
& pulse width of 9mS.
Corporation standard of
Q/DKBA1124-2002
Drop On 6 sides for one time each at the height of 100cm.
No effect on electric
performance of module.
Dust-proof Dust-proof function is needed.
X. Mechanical Characteristics
1. Outline dimensions
L×W×H = 482.6×262(With handle)×43.4 Unitmm

Содержание