SNR RDC-48-540-STD [4/15] V electrical characteristics
![SNR RDC-48-540-STD [4/15] V electrical characteristics](/views2/1978797/page4/bg4.png)
Page 4 of 15
V. Electrical Characteristics
1 Input Characteristics
No. Items Technical Specifications Unit Remarks
1.1 Input rated voltage 100-240 Vac
1.2 Input voltage range 90-264 Vac Rated input, full load
1.3
Input voltage range
limiting
90-280 Vac
1.4 Input voltage frequency 47-63 Hz
1.5 Input Current <8.4 A
Lowest input voltage, rated
load
1.6 Input Shock Current <50 A
Cold start-up, max input
voltage
2 Output Characteristics
No. Items Technical Requirements Unit Remarks
2.1 Min output current 0 A
2.2 Max output current 10 A Forced air cooling
2.3 Output voltage range +54±0.5 Vdc
Power supply voltage refers
to the voltage after two
rectified modules are
integrated (voltage drop
inside distribution unit is
0.3V )
2.4 Output ripple & noise ≤200 mVp-p
Rated load, frequency band
is limited to 20MHz
2.5 PFC >0.95
Input voltage 264 -280Vac,
it is OK for PFC to be not
satisfied with 0.95
2.6 Output power 270(typical value) W
Air cooling, for single
module
2.7 Efficiency >80%
Rated input voltage (220Vac)
rated load
2.8
Turn-on output delay
≤5 S
Vin=220Vac
2.9
Output rising time
≤100
mS
Output voltage rises
from 10% to 90%, rated
load.
2.10
Output holding time
>10
mS
2.11 Turn on/off overshoot ≤5 %Vo
Overshoot
≤5 %Vo
2.12
Transient
Response
Recovery
time
≤200 µS
25%—50%—25%
or 50%—75%—50%
load change
2.13 Temperature coefficient ±0.02
%/℃
2.0V±0.2
Output 5A
2.14
LS terminal voltage (for
single module)
1.0V±0.2
V
Output 2.5A
Содержание
- Contents 1
- I general 2
- Ii main specifications 2
- Iii quoted standards 2
- Iv environmental conditions 3
- Input characteristics 4
- Output characteristics 4
- V electrical characteristics 4
- Battery management characteristics 5
- Vi other requirements 6
- Vii safety emc 6
- Viii alert monitor interface 7
- Ix environmental testing requirements 8
- X mechanical characteristics 8
- Input port definition 10
- Output port definition 10
- 2 monitoring interface 12
- A1 a10 54v is the positive terminal of the 54v dc input 12
- A11 empty 12
- B1 b7 b11 empty 12
- B2 b6 54v is the positive terminal of the 54v dc input 12
- C1 state1 is the collector input of opt on for the rectification module 1 high resistant when the module 12
- C2 c6 empty 12
- C7 c11 gnd is the negative terminal of the dc 54v input 12
- D1 acstate is the emitter input of the warning opt for ac power shut down it should be high 12
- D10 d11 gnd is the negative terminal of 54v dc input 12
- D2 d3 empty 12
- D4 clonx is the ttl electric level output for battery current limitation value control high electric level 12
- D5 vdd is the 5v voltage output 12
- D6 batfuse is the ttl electric level input for battery fuse burn warning high electric level for warning 12
- D7 empty 12
- D8 load1fuse is the 23v input for no 1 circuit load fuse burn warning 23v for warning status and low 12
- D9 load2fuse is the 23v input for no 2 circuit load fuse burn warning 23v for warning status and low 12
- E1 clistate2 is the collector input of overload opt for rectification module 2 high resistance for 12
- E2 alm1 is the collector input of output warning opt of rectification module 1 high resistance for 12
- E3 clistate1 is the collector input of overload opt for rectification module 1 high resistance for 12
- E4 state2 is the collector input of opt on for the rectification module 2 high resistant when the module 12
- Electric level for normal operation 12
- Is disconnected while low electric level when connected 12
- Overload status and low electric level for normal operation 12
- Page 12 of 15 12
- Resistance in warning status and should be high electric level in normal operation 12
- Status and low electric level for normal operation 12
- Warning status and low electric level for normal operation 12
- Would change it default value while low electric level keep it remain the same 12
- Xi package transportation and storage 14
- Xii reliability requirements 15
- Xiii attentions 15
Похожие устройства
- SNR UPS-ONRT-25-INTXL33 Паспорт
- SNR UPS-ONRT-25-INTXL33 Инструкция
- SNR UPS-ONRM-2000-X72 Паспорт
- SNR UPS-ONRM-2000-X72 Инструкция
- SNR UPS-ONRT-15-INTXL33 Паспорт
- SNR UPS-ONRT-15-INTXL33 Руководство пользователя
- SNR UPS-ONT-10000-INT Паспорт
- SNR UPS-ONT-10000-INT Руководство пользователя
- SNR UPS-ONT-020-BXL31 Паспорт
- SNR UPS-ONT-020-BXL31 Руководство пользователя
- SNR UPS-BCT-3000-B72 Паспорт
- SNR UPS-ONT-015-BXL31 Руководство пользователя
- SNR UPS-ONRM-2000-XL72 Паспорт
- SNR UPS-ONRM-2000-XL72 Руководство пользователя
- SNR UPS-ONT-6000-INTXL Паспорт
- SNR UPS-ONT-10000-INTXL Паспорт
- SNR UPS-ONT-010-BXL31 Руководство пользователя
- SNR UPS-ONPM-50SMX33 Паспорт
- SNR UPS-ONRT-090-15CMX33 Руководство пользователя
- SNR UPS-ONRT-040-10CMX33 Инструкция