VI. Other Requirements
No. Items Requirements Remarks
1 Noise Less than 50dB
2 Hot swappable
Support hot swappable. No influence to input/ output
when hot swap.
3 Failure separation
Reliable separation when one module fails, and no
influence to the other module.
4
Remote compensation
None
5
Voltage drop for
distribution unit
Less than 0.3V
Differential mode 3KA/common mode 5KA for ± 5
times.
6
Lightning protection
Series connection fuse with protective loop.
Waveform 8/20us,no
destruction
Remarks: Requirements for noise testing:
1. Put testing sample with full arrangement on the state of non- package and non-electricity to the center of
EMC darkroom.
2. Wipe off all the background noise in the darkroom.
3. Test the sample noise when electricity is put on and fan rotates with max speed.
4. Make psophometer 0.6m away from shelf, and 1.5m from ground, and then test four facets of sample.
VII. Safety & EMC
No. Items Criteria Remarks
Input—Output 3000Vac/15mA/1min
Input—Ground 1800Vac/10mA/1min
1
Dielectric
Strength
Output—Ground 500Vac/10mA/1min
No flashover and
breakdown. It is right to use
DC which is peak of AC
voltage.
Input—Output ≥10MΩ@500Vdc
Input—Ground ≥10MΩ@500Vdc
2
Isolation
Resistance
Output—Ground ≥10MΩ@500Vdc
Under normal atmospheric
pressure, relative humidity is
90%, testing voltage is
500Vdc.
3 Ground Fault Current <3.5mA
Input to ground
4 Resistance to ground <0.1Ω
Connect 40A/2min to the
metal case and NW
5 Safety
Design meets UL60950 and EN60950,
and final product meets TUV, CE and UL
UL60950/EN60950/
CE MARK
CE CLASS B EN55022
RE CLASS B EN55022
ESD LEVEL 3 EN61000-4-2
RS 10V/m EN61000-4-3
CS 10V EN61000-4-6
EFT LEVEL 3 EN61000-4-4
6
EMC
SUGER LEVEL 4 EN61000-4-5
Содержание
- Contents 1
- I general 2
- Ii main specifications 2
- Iii quoted standards 2
- Iv environmental conditions 3
- Input characteristics 4
- Output characteristics 4
- V electrical characteristics 4
- Battery management characteristics 5
- Vi other requirements 6
- Vii safety emc 6
- Viii alert monitor interface 7
- Ix environmental testing requirements 8
- X mechanical characteristics 8
- Input port definition 10
- Output port definition 10
- 2 monitoring interface 12
- A1 a10 54v is the positive terminal of the 54v dc input 12
- A11 empty 12
- B1 b7 b11 empty 12
- B2 b6 54v is the positive terminal of the 54v dc input 12
- C1 state1 is the collector input of opt on for the rectification module 1 high resistant when the module 12
- C2 c6 empty 12
- C7 c11 gnd is the negative terminal of the dc 54v input 12
- D1 acstate is the emitter input of the warning opt for ac power shut down it should be high 12
- D10 d11 gnd is the negative terminal of 54v dc input 12
- D2 d3 empty 12
- D4 clonx is the ttl electric level output for battery current limitation value control high electric level 12
- D5 vdd is the 5v voltage output 12
- D6 batfuse is the ttl electric level input for battery fuse burn warning high electric level for warning 12
- D7 empty 12
- D8 load1fuse is the 23v input for no 1 circuit load fuse burn warning 23v for warning status and low 12
- D9 load2fuse is the 23v input for no 2 circuit load fuse burn warning 23v for warning status and low 12
- E1 clistate2 is the collector input of overload opt for rectification module 2 high resistance for 12
- E2 alm1 is the collector input of output warning opt of rectification module 1 high resistance for 12
- E3 clistate1 is the collector input of overload opt for rectification module 1 high resistance for 12
- E4 state2 is the collector input of opt on for the rectification module 2 high resistant when the module 12
- Electric level for normal operation 12
- Is disconnected while low electric level when connected 12
- Overload status and low electric level for normal operation 12
- Page 12 of 15 12
- Resistance in warning status and should be high electric level in normal operation 12
- Status and low electric level for normal operation 12
- Warning status and low electric level for normal operation 12
- Would change it default value while low electric level keep it remain the same 12
- Xi package transportation and storage 14
- Xii reliability requirements 15
- Xiii attentions 15
Похожие устройства
- SNR UPS-ONRT-25-INTXL33 Паспорт
- SNR UPS-ONRT-25-INTXL33 Инструкция
- SNR UPS-ONRM-2000-X72 Паспорт
- SNR UPS-ONRM-2000-X72 Инструкция
- SNR UPS-ONRT-15-INTXL33 Паспорт
- SNR UPS-ONRT-15-INTXL33 Руководство пользователя
- SNR UPS-ONT-10000-INT Паспорт
- SNR UPS-ONT-10000-INT Руководство пользователя
- SNR UPS-ONT-020-BXL31 Паспорт
- SNR UPS-ONT-020-BXL31 Руководство пользователя
- SNR UPS-BCT-3000-B72 Паспорт
- SNR UPS-ONT-015-BXL31 Руководство пользователя
- SNR UPS-ONRM-2000-XL72 Паспорт
- SNR UPS-ONRM-2000-XL72 Руководство пользователя
- SNR UPS-ONT-6000-INTXL Паспорт
- SNR UPS-ONT-10000-INTXL Паспорт
- SNR UPS-ONT-010-BXL31 Руководство пользователя
- SNR UPS-ONPM-50SMX33 Паспорт
- SNR UPS-ONRT-090-15CMX33 Руководство пользователя
- SNR UPS-ONRT-040-10CMX33 Инструкция