Product Description
High Performance 10-20k UPS
10
TVS&RFI/E
MI filter
REC/PFC INVERTER
CHG
BATT
BYPA
SS
Fig 1- 7:
ECO Mode
Frequency Converter Mode
In this mode, input and output nominal frequency is different, and the bypass is forbidden to use.
NOTICE: if overload timeout, UPS will shutdown output.
NOTICE: the load should be derated to 50% and below.
Self Aging Mode
If users want to burn in UPS without load, could set the UPS as Self Aging Mode, in this mode, the
current flow through rectifier, inverter, and back to input through bypass. It needs only 5% loss to
burn in UPS with 100% load. Shown as Fig 1-8.
TVS&RFI/E
MI filter
rectifier/PFC INVERTER
CHG
BATT
BYPA
SS
input
Fig 1- 8:
Self Aging Mode
1.7 Product Specification
1. General Specification
Model
10KL
15KL
20KL
Power Rating
10KVA/10KW
15KVA/15KW
20KVA/20KW
Frequency (Hz)
50/60