Legrand MegaLine Rack 1250 [42/132] Customising the ups operating mode

Legrand MegaLine Rack 1250 [42/132] Customising the ups operating mode
42
®
4. Customising the UPS operating mode
4.5 UPS Setup
Output
Input
Voltage
Frequency
N+x Redundancy
PLL Enable
Extended PLL Range
ð
ð
Voltage To set the UPS output voltage (V)
Frequency
To set the UPS output frequency (Hz)
Nominal Value: to set a numerical value for the output
frequency (50 or 60)
Auto Selection:
If enabled, the UPS reads the frequency of the input
voltage and then synchronises the output to the same
value.
If disabled, the UPS uses the set Nominal Value.
N+x Redundancy
To set the number of redundant boards
(refer to NB: Redundancy Settings)
PLL Enable
If enabled, the UPS synchronises the output sine wave
with the input
If disabled, the output voltage is not synchronised with
the input. This is indicated by the flashing of the status
warning light (green)
Extended PLL
Range
If enabled, the UPS synchronises the output voltage with
the input for variations in frequency of +/-14%
the nominal value.
If disabled, the PLL is synchronised for variations in
frequency of +/-2%.
NB: Redundancy Settings
This function is used to manage the redundancy of the power modules. For example: a load requires N power modules; X power
modules must be added to achieve N+X redundancy.
If the load applied exceeds the power supplied by N modules during operation, the UPS will signal the lack of redundancy.
A numerical example is given below:
NB: PLL Settings.
The PLL function ensures the UPS output frequency is synchronised with the input so that the changeover at zero takes
place at the exact same time. Should the by-pass intervene, e.g. due to unanticipated loads, input-output synchronisation
is guaranteed.
Load
Power
boards
Total
power (W)
Redundancy
Redundancy
alarm (W)
Overload
alarm (W)
3700 3 3750 0 no 3750
3700 4 5000 1 3750 5000
1500 4 5000 2 2500 5000
1000 4 5000 3 1250 5000

Содержание

Похожие устройства

Скачать