Legrand TRIMOD HE 15 kVA [14/14] En 62040 1 general and safety requirements for ups used in operator access areas

Legrand TRIMOD HE 15 kVA [14/14] En 62040 1 general and safety requirements for ups used in operator access areas
14 di 14
6.5 Battery
Type
Lead Acid, sealed, free maintenance VRLA
Unit Capacity
7,2 or 9 Ah (12V)
Nominal UPS Battery Voltage
240 Volt DC
Battery charger type
PWM hi efficiency, one in each power module
Charging Cycle
Intelligent with boost charge and advanced management
Max Charging Current
2,5 A each power module
6.6 Environmental specs
Noise level @ 1m
42 ÷ 46 dBA
Working temperature range
from 0°C to +40°C
Stock temperature range
from -20°C to +50°C (excluded batteries)
Humidity range
20-95% not condensing
Protection degree
IP21
6.7 Mechanical an Michellaneous
Net Weight with out batteries
4
120 kg
Dimensions (W×HxD)
5
1 x (414 x 1345 x 628) (mm) [1 x (414 x 1650 x 628) (mm)]
Colour
RAL 7016
Technology rectifier/booster/inverter
MOSFET/IGBT
Communication Interface
2 serial port RS232, 1 logicic level port, 4 Dry contacts port
Input/Output connections
3P + N + PE Connectors on omega bar
Number of Installed Power Modules
3 of 5000 VA
Standards
EN 62040-1, EN 62040-2, EN 62040-3
The UPS Manifacturer Company must have ISO9001 certification for development, production, and
services.
1 REFERENCE STANDARDS
The static uninterruptible power system must be designed and produced in compliance with the following
international standards:
EN 62040-1 “General and safety requirements for UPS used in operator access areas"
EN 62040-2 “Electromagnetic compatibility requirements (EMC)”
EN 62040-3 “Performance requirements and test methods”
The UPS must have CE marking in accordance with European Directives 73/23, 93/68, 89/336, 92/31,
93/68.