Legrand TRIMOD HE 15 kVA [14/14] En 62040 1 general and safety requirements for ups used in operator access areas
![Legrand TRIMOD HE 15 kVA [14/14] En 62040 1 general and safety requirements for ups used in operator access areas](/views2/1165524/page14/bge.png)
14 di 14
6.5 Battery
Type
Lead Acid, sealed, free maintenance VRLA
Unit Capacity
7,2 or 9 Ah (12V)
Nominal UPS Battery Voltage
240 Volt DC
Battery charger type
PWM hi efficiency, one in each power module
Charging Cycle
Intelligent with boost charge and advanced management
Max Charging Current
2,5 A each power module
6.6 Environmental specs
Noise level @ 1m
42 ÷ 46 dBA
Working temperature range
from 0°C to +40°C
Stock temperature range
from -20°C to +50°C (excluded batteries)
Humidity range
20-95% not condensing
Protection degree
IP21
6.7 Mechanical an Michellaneous
Net Weight with out batteries
4
120 kg
Dimensions (W×HxD)
5
1 x (414 x 1345 x 628) (mm) [1 x (414 x 1650 x 628) (mm)]
Colour
RAL 7016
Technology rectifier/booster/inverter
MOSFET/IGBT
Communication Interface
2 serial port RS232, 1 logicic level port, 4 Dry contacts port
Input/Output connections
3P + N + PE Connectors on omega bar
Number of Installed Power Modules
3 of 5000 VA
Standards
EN 62040-1, EN 62040-2, EN 62040-3
The UPS Manifacturer Company must have ISO9001 certification for development, production, and
services.
1 REFERENCE STANDARDS
The static uninterruptible power system must be designed and produced in compliance with the following
international standards:
• EN 62040-1 “General and safety requirements for UPS used in operator access areas"
• EN 62040-2 “Electromagnetic compatibility requirements (EMC)”
• EN 62040-3 “Performance requirements and test methods”
The UPS must have CE marking in accordance with European Directives 73/23, 93/68, 89/336, 92/31,
93/68.
4
The weigh depends by the number of the installed batteries accordingly with the required autonomy.
5
The battery cabient dimension can change depending battery set accordingly with the required autonomy.
Содержание
- For three phase ups on line double conversion vfi 1
- Kva 15 kw 1
- Tender technical specification 1
- Description of the system 6 2
- General requirements 4 2
- Generali specifications 4 2
- Operating principle 8 2
- Control panel and display 10 3
- Reference standards 14 3
- Technical specifications 13 3
- General requirements 4
- Generali specifications 4
- X n p p 5
- Description of the system 6
- Bypass activation sensitivity adjustment 8
- Inverter stopping 8
- Normal service condition 8
- Operating principle 8
- Overload 8
- After a blackout 9
- Inverter stopping in a power module 9
- Maintenance bypass 9
- Start up on bypass 9
- Asynchronous operation 10
- Control panel and display 10
- Frequency converter 10
- Genset 10
- Operation with a genset or as a frequency converter 10
- Adjustments 11
- Buzzer silencer 11
- Controls 11
- Functions and quitting 11
- Keyboard to browse the menus on the display set parameters confirming the selected 11
- Measurements 11
- Shutdown in an emergency the button must remain depressed for at least 3 seconds 11
- Signals and alarms 11
- The ups can manage the following measurements and show the relevant values on the display 11
- The ups has the following controls 11
- The ups must be equipped with a lighted operating status indicator with traffic light coding not smaller that 600x300 mm as well as a buzzer able to immediately indicate the following operating conditions 11
- The will ups allow the following adjustments to be made and shown on the display 11
- Ups secure powering protection against accidental powering 11
- Ups stopping to prevent accidental power offs while allowing the ups to be quickly 11
- E p o emergency power off 12
- Interfaces 12
- Miscellaneous equipment 12
- Rs232 serial port 12
- General specifications 13
- Item data 13
- Output in battery run dc ac 13
- Output with mains ac ac 13
- Technical specifications 13
- En 62040 1 general and safety requirements for ups used in operator access areas 14
- En 62040 2 electromagnetic compatibility requirements emc 14
- En 62040 3 performance requirements and test methods 14
- Reference standards 14
- The static uninterruptible power system must be designed and produced in compliance with the following international standards 14
- The ups manifacturer company must have iso9001 certification for development production and services 14
- The ups must have ce marking in accordance with european directives 73 23 93 68 89 336 92 31 the ups must have ce marking in accordance with european directives 73 23 93 68 89 336 92 31 93 68 14
Похожие устройства
- Legrand TRIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 20 kVA Технические характеристики
- Legrand TRIMOD HE 30 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 30 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 30 kVA Технические характеристики
- Legrand TRIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 40 kVA Технические характеристики
- Legrand TRIMOD HE 60 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 60 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 60 kVA Технические характеристики
- Legrand ARCHIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 20 kVA Технические характеристики
- Legrand ARCHIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 40 kVA Технические характеристики
- Legrand ARCHIMOD HE 60 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 60 kVA Инструкция по эксплуатации