2.4 Scalabilty
The modularity of the UPS must allow to increase the back-up time on site, simply adding battery
drawers. The upgrade will not require factory modifications and will not need dedicated special tools.
2.5 Architetture
The architecture of the UPS must be parallel distributed, to be more precise, the load will be shared
between all power modules in each phase. In this way, during normal run, no power module is inactive or
in standby. In a redundant configuration, if one moduel fails all the others ones will take the relevant load
without any interruptions or transfer time at the output of the UPS. In case one module failure the power
is guaranteed by the others modules and the supplied power will been s follows:
n
xn
PP
nomout
)( −
=
in single phase configuration
and
n
xn
PP
nomout
)3( −
=
in three phase configuration
where
•
nom
P
is the nominal power of the UPS;
• is the power supplied by the UPS with one module out of order;
•
n
is the number of installed power modules inside the UPS;
• x is the number of power modules out of order;
2.6 Adaptability
The UPS should be equipped with a distribution system, for cable connections, which allows the desired
In/Out phase configuration by simple jumper connections, without any components replacement or
factory settings.
Thanks to this system, it will be possible to set, independently, In/Out phase configurations as
three/three, three/single, single/single and single/three. Furthermore it will be possible to set the output
as three independent single-phase lines, and due to adequate dimensioning, to realize individual
redundancy for each single line.
The In/Out phase configuration will be always possible on site accordingly with the application in terms of
utility and loads.
out
P
Содержание
- For three phase ups on line double conversion vfi 1
- Kva 15 kw 1
- Tender technical specification 1
- Description of the system 6 2
- General requirements 4 2
- Generali specifications 4 2
- Operating principle 8 2
- Control panel and display 10 3
- Reference standards 14 3
- Technical specifications 13 3
- General requirements 4
- Generali specifications 4
- X n p p 5
- Description of the system 6
- Bypass activation sensitivity adjustment 8
- Inverter stopping 8
- Normal service condition 8
- Operating principle 8
- Overload 8
- After a blackout 9
- Inverter stopping in a power module 9
- Maintenance bypass 9
- Start up on bypass 9
- Asynchronous operation 10
- Control panel and display 10
- Frequency converter 10
- Genset 10
- Operation with a genset or as a frequency converter 10
- Adjustments 11
- Buzzer silencer 11
- Controls 11
- Functions and quitting 11
- Keyboard to browse the menus on the display set parameters confirming the selected 11
- Measurements 11
- Shutdown in an emergency the button must remain depressed for at least 3 seconds 11
- Signals and alarms 11
- The ups can manage the following measurements and show the relevant values on the display 11
- The ups has the following controls 11
- The ups must be equipped with a lighted operating status indicator with traffic light coding not smaller that 600x300 mm as well as a buzzer able to immediately indicate the following operating conditions 11
- The will ups allow the following adjustments to be made and shown on the display 11
- Ups secure powering protection against accidental powering 11
- Ups stopping to prevent accidental power offs while allowing the ups to be quickly 11
- E p o emergency power off 12
- Interfaces 12
- Miscellaneous equipment 12
- Rs232 serial port 12
- General specifications 13
- Item data 13
- Output in battery run dc ac 13
- Output with mains ac ac 13
- Technical specifications 13
- En 62040 1 general and safety requirements for ups used in operator access areas 14
- En 62040 2 electromagnetic compatibility requirements emc 14
- En 62040 3 performance requirements and test methods 14
- Reference standards 14
- The static uninterruptible power system must be designed and produced in compliance with the following international standards 14
- The ups manifacturer company must have iso9001 certification for development production and services 14
- The ups must have ce marking in accordance with european directives 73 23 93 68 89 336 92 31 the ups must have ce marking in accordance with european directives 73 23 93 68 89 336 92 31 93 68 14
Похожие устройства
- Legrand TRIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 20 kVA Технические характеристики
- Legrand TRIMOD HE 30 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 30 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 30 kVA Технические характеристики
- Legrand TRIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 40 kVA Технические характеристики
- Legrand TRIMOD HE 60 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 60 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 60 kVA Технические характеристики
- Legrand ARCHIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 20 kVA Технические характеристики
- Legrand ARCHIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 40 kVA Технические характеристики
- Legrand ARCHIMOD HE 60 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 60 kVA Инструкция по эксплуатации