Legrand TRIMOD HE 15 kVA Технические характеристики онлайн [7/14] 151430
7 di 14
! Automatically transfer back the load from the mains to the inverter as soon the anomalous
event expires;
! Automatically disable the bypass function in case of output voltage and Mains are not
synchronized.
3.2 COMMAND BOARD
The Command board must be equiped with microprocessor of suitable computation power. This
command board must manage all functions of the UPS and will execute the following jobs:
1. automatic recognition of the number of connected modules;
2. automatic setting of the maximum reactive power that can be provided on the output;
3. individual serial communication with the power modules by a dedicated line;
4. recognition of a faulty module and diagnosis of the relevant fault;
5. synchronization of the output voltage with the input voltage;
6. generation of a reference sinewave curve to form the output voltage wave;
7. control of the PFC, inverter and booster circuits in each power module;
8. management of the automatic bypass;
9. management of the battery runtime (see relative section);
10. management and recognition of the signals and measurements from each module;
11. management of the user interface (see relative section);
12. management and memorizing of UPS history parameters and data;
13. alarm and events memory with association of the time and date of the events themselves.
3.3 Batteries
3.3.1 Battery type
The hermetic, maintenance-free stationary lead batteries are housed in the UPS and/or in one of more
cabinets of the same shape and size as that of the UPS itself. The positive and negative battery
connections are protected by an adequate fuse-holder isolating switch.
3.3.2 Battery Module (Drawer)
The complete set of batteries consists of at least 20 units so as to obtain an overall 240 V nominal
voltage (direct voltage).
A drawer comprises five 12 V 7.2 Ah or 9 Ah batteries connected in series. The drawer must complies
with CEI-EN 60950 standards governing electrical safety, which requires the use of adequate protections
and particular care when dangerous voltages higher than 50 Vdc are present and direct contacts are
possible.
The runtime can be increased to a further extent by adding more battery drawers in multiples of four,
using both the housings in the UPS and those pre-engineered in the additional “modular cabinets”.
3.3.1
Battery management
The following functions must be available:
Conduction of the battery test either automatically or upon the user’s request.
Battery efficiency test conducted by making an automatic full discharge at programmed or periodic
frequencies, as required by the user. The battery is discharged by use of an appropriate algorithm with
discharge curve control so as to monitor the performance and status of the batteries.
Calculation of the residue battery runtime during the discharge phase, depending on the load applied.
Содержание
- For three phase ups on line double conversion vfi 1
- Kva 15 kw 1
- Tender technical specification 1
- Description of the system 6 2
- General requirements 4 2
- Generali specifications 4 2
- Operating principle 8 2
- Control panel and display 10 3
- Reference standards 14 3
- Technical specifications 13 3
- General requirements 4
- Generali specifications 4
- X n p p 5
- Description of the system 6
- Bypass activation sensitivity adjustment 8
- Inverter stopping 8
- Normal service condition 8
- Operating principle 8
- Overload 8
- After a blackout 9
- Inverter stopping in a power module 9
- Maintenance bypass 9
- Start up on bypass 9
- Asynchronous operation 10
- Control panel and display 10
- Frequency converter 10
- Genset 10
- Operation with a genset or as a frequency converter 10
- Adjustments 11
- Buzzer silencer 11
- Controls 11
- Functions and quitting 11
- Keyboard to browse the menus on the display set parameters confirming the selected 11
- Measurements 11
- Shutdown in an emergency the button must remain depressed for at least 3 seconds 11
- Signals and alarms 11
- The ups can manage the following measurements and show the relevant values on the display 11
- The ups has the following controls 11
- The ups must be equipped with a lighted operating status indicator with traffic light coding not smaller that 600x300 mm as well as a buzzer able to immediately indicate the following operating conditions 11
- The will ups allow the following adjustments to be made and shown on the display 11
- Ups secure powering protection against accidental powering 11
- Ups stopping to prevent accidental power offs while allowing the ups to be quickly 11
- E p o emergency power off 12
- Interfaces 12
- Miscellaneous equipment 12
- Rs232 serial port 12
- General specifications 13
- Item data 13
- Output in battery run dc ac 13
- Output with mains ac ac 13
- Technical specifications 13
- En 62040 1 general and safety requirements for ups used in operator access areas 14
- En 62040 2 electromagnetic compatibility requirements emc 14
- En 62040 3 performance requirements and test methods 14
- Reference standards 14
- The static uninterruptible power system must be designed and produced in compliance with the following international standards 14
- The ups manifacturer company must have iso9001 certification for development production and services 14
- The ups must have ce marking in accordance with european directives 73 23 93 68 89 336 92 31 the ups must have ce marking in accordance with european directives 73 23 93 68 89 336 92 31 93 68 14
Похожие устройства
- Legrand TRIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 20 kVA Технические характеристики
- Legrand TRIMOD HE 30 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 30 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 30 kVA Технические характеристики
- Legrand TRIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 40 kVA Технические характеристики
- Legrand TRIMOD HE 60 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 60 kVA Инструкция по эксплуатации
- Legrand TRIMOD HE 60 kVA Технические характеристики
- Legrand ARCHIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 20 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 20 kVA Технические характеристики
- Legrand ARCHIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 40 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 40 kVA Технические характеристики
- Legrand ARCHIMOD HE 60 kVA Инструкция по эксплуатации
- Legrand ARCHIMOD HE 60 kVA Инструкция по эксплуатации