CONEL CDA 70 [12/43] Cda70 modem description

CONEL CDA 70 [12/43] Cda70 modem description
CDA70 MODEM DESCRIPTION
12
Circuit example of the meter with modem CDA70 with data cable length more than 10 m:
M-BUS data cable more than 10 m it is need to use over-voltage protection on CDA 70
modem side!
External or internal power supply of expansion port M-BUS it is can evoke by wiring
of the jumper. For details see chapter 2.8.
2.5.3. Connection of PORT2 connectors (RS485G)
Panel socket RJ45
Pin
number
Signal
mark
Description Data flow direction
1 GND Signal and supply ground
2 GND Signal and supply ground
3 TxRx- RS485 B (-) Input/Output
4 TxRx+ RS485 A (+) Input/Output
5 TxRx- RS485 B (-) Input/Output
6 TxRx+ RS485 A (+) Input/Output
7 +12V EXT External power supply +10,8 ÷ +15,6V
8 +12V EXT External power supply +10,8 ÷ +15,6V
ATTENTION! External supply is for converter RS485G!
The converter must have external power supply because of galvanic separated.
DC
Meter
SGND
MBUS (-)
MBUS (+)
Meter
SGND
MBUS (-)
MBUS (+)
Modem CDA70
Pin 1 – SGND
Pin 2 – SGND
Pin 3 – MBUS (-)
Pin 4 – MBUS (+)
Pin 5 – MBUS (-)
Pin 6 – MBUS (+)
Pin 7 – +12V EXT
Pin 8 – +12V EXT
+
1X
2X
1Y
2Y
OVPM-21

Содержание

Скачать