Moxa ioLogik E1512-M12-CT-T [20/62] Ethernet configuration

Moxa ioLogik E1510-M12-T [20/62] Ethernet configuration
ioLogik E1500 Series Using the Web Console
3-4
The Communication Watchdog activates Safe Mode after a specified amount of time has passed following a loss
of network connectivity. Safe Mode is designed especially for products that have output channels to output a
suitable value or status when the ioLogik E1500 cannot be controlled by a remote PC (due to network failure,
for example). By default, the Watchdog is disabled. Users can configure how each output channel responds on
the I/O Settings page.
To enable the Watchdog, check Enable connection watchdog, set the timeout value, and then restart the
server. With Watchdog enabled, the ioLogik E1500 will enter Safe Mode after there is a disruption in
communication that exceeds the specified time limit.
For easier location of devices when troubleshooting, enable the remote control of LEDs on the E1500 series
devices by selecting Enable I/O Locate to allow remote toggling of the Ready LED from off to flashing.
Ethernet Configuration
On the Ethernet Configuration page, you can set up a static or dynamic IP address for the ioLogik E1500, and
configure the subnet mask and gateway address.
User-defined Modbus Addressing
The input and output addresses can be configured in a different format on a specific settings page. Check the
Enable User-defined Modbus Addressing box, select the Modbus function, and then configure the start
address of each item.