ioLogik E1500 Series Using the Web Console
3-11
In Pulse Output mode, you can specify the ON Width and OFF width to generate a square wave.
Pulse Width unit = 1 ms, range = 1-65535
When configuring individual channels, if the Power On Setting is selected the Pulse Output will start as soon
as the ioLogik E1500 is powered on; if the Safe Status Setting is selected, the Pulse Output will start only
once the E1500 has entered Safe Status mode. In contrast, when neither of these setting is selected and the
Pulse Start field is selected, the ioLogik E1500 will automatically stop the Pulse Output when either the ioLogik
E1500 is Powered On or when it enters Safe Status mode. (Note: Safe Status is controlled by the
Communication Watchdog under General Settings, which is disabled by default. If the Communication
Watchdog is disabled, the ioLogik E1500 will never enter Safe Mode and your Safe Status settings will have no
effect.)