Moxa ioLogik E1512-M12-CT-T [7/62] Digital input

Moxa ioLogik E1510-M12-CT-T [7/62] Digital input
ioLogik E1500 Series Introduction to the ioLogik E1500
1-3
Environmental Limits
Operating Temperature:
-40 to 85°C (-40 to 185°F)
Storage Temperature:
-40 to 85°C (-40 to 185°F)
Ambient Relative Humidity:
5 to 95% (non-condensing)
Altitude:
Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to function properly at higher altitude
s.
Conformal Coating:
Applies only to -CT models
Standards and Certifications
Safety:
UL 508
EMI:
EN 61000-3-2, EN 61000-3-3, EN 61000-6-4, FCC Part 15 Subpart B Class A
EMS:
EN 55024, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4,
EN 61000
-4-5, EN 61000-4-6, EN 61000-4-8, EN 61000-4-11,
EN 61000
-6-2
Shock:
IEC 60068-2-27
Freefall:
IEC 60068-2-32
Vibration:
IEC 60068-2-6
Green Product: RoHS, CRoHS, WEEE
Note: Please check Moxa’s website for the most up
-to-date certification status.
Rail Traffic:
EN 50155*, EN 50121-3-2, EN 50121-4
*Complies with a portion of EN 50155 specifications. Please contact Moxa or a Moxa distributor for
details.
Warranty
Warranty Period:
5 years
Details:
See www.moxa.com/warranty
ioLogik E1510-T
Inputs and Outputs
Digital Inputs:
12 channels (channel-to-channel isolation)
Isolation:
3K VDC or 2K Vrms
Digital Input
Sensor Type:
Wet Contact (NPN or PNP), Dry Contact
I/O Mode:
DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to GND):
• On: 0 to 3 VDC
• Off: 10 to 30 VDC
Counter Frequency:
250 Hz
Digital Filtering Time Interval:
Software Configurable
(minimum: 1 millisecond)
Power Requirements
Power Consumption:
163 mA @ 24 VDC