ioLogik E1500 Series Using the Web Console
3-7
I/O Settings
DI Channels
The status of each DI (digital input) channel appears on the I/O Setting: DI Channels page.
You can also configure each channel’s digital input mode and parameters by clicking on the channel. DI
Channels can operate in DI mode or Event Counter mode.
Activate Event Counter mode by selecting the Counter Start field and configuring the Counter Trigger to
either Lo to Hi, Hi to Lo, or Both. When the Counter Start field is not selected you can still activate the counter
by using the Modbus command.
NOTE
Make sure that the Counter Filter is not set to 0; otherwise, the counter will never be activated.
When configuring individual channels, if the Power On Setting is selected the counter will start as soon as the
ioLogik E1500 is powered on; if the Safe Status Setting is selected, the counter will start only once the E1500
has entered Safe Status mode. In contrast, When neither of these settings are selected, but Counter Start is,
the ioLogik E1500 will automatically stop the Counter when either the ioLogik E1500 is Powered On or when it
enters Safe Status mode. (Note: Safe Status is controlled by the Communication Watchdog under General
Settings, which is disabled by default. If the Communication Watchdog is disabled, the ioLogik E1500 will never
enter Safe Mode and your Safe Status settings will have no effect.)