Moxa MxNVR-IA8-T [52/61] Digital input

Moxa MxNVR-IA8 [52/61] Digital input
Moxa MxNVR-IA8 System Configuration
4-23
Digital Input
6 digital inputs are provided by the MxNVR-IA8 for linking with alarm detection devices, such as sensors.
Setting Description Default
Enable digital input
alarm
Enable or disable the digital input alarm. Disable
Trigger Conditions
Setting Description Default
High The DI is always in the “High” state after an alarm is detected. Disable
Low The DI is always in the “Low” state after an alarm is detected. Enable
Rising The DI works from the “Low” state to “High” state and then
back to the Low” state when an alarm is detected.
Disable
Falling The DI works from the High” state toLow” state and then
back to theHigh” state when an alarm is detected.
Disable
NOTE Refer to Chapter 1 to see the DI specifications.
Trigger Actions
Setting Description Default
Trigger DO1 alarm Once this DI is triggered, the DO1 alarm will be activated Disable
Trigger DO2 alarm Once this DI is triggered, the DO2 alarm will be activated Disable
Send message via HTTP
Event Servers
Once this DI is triggered, the MxNVR will send the message set
in HTTP Action Setting to the HTTP event servers, which are set
in the Network/ HTTP Event Server page.