SinePower Troubleshooting
29
12 Troubleshooting
!
I
The “Load Status” LED (fig. 6 3, page 4 and fig. 7 3,page 5) lights up red to
indicate the fault:
WARNING!
Do not open the device. You risk sustaining an electric shock by doing
this.
NOTE
If you have detailed questions on the specifications of the inverter
please contact the manufacturer (addresses on the back of the instruc-
tion manual).
LED display Cause Remedy
Quick flash Input voltage is too high Check the input voltage and reduce
it.
Slow flash Input voltage too low The battery needs recharging.
Check the cables and connections.
Occasional flash Overheating Switch off the inverter and the con-
sumer.
Wait 5 to 10 minutes and switch the
inverter on again without any elec-
tric consumers.
Reduce the load and make sure the
inverter has better ventilation. Then
switch the consumer back on.
Constantly lit Short circuit or reversed
polarity
Excessive load
Switch off the inverter and remove
the consumer.
Then switch the inverter back on
without the consumer. If no
excessive load is now shown, then
there is a short circuit in the con-
sumer or the total load was higher
than the power specified on the
data sheet. MSI1812T and
MSI1824T: The fuse in the device
must be pressed in again by hand
after it is triggered.
Check the cables and connections.
MSI900-1800--IO-16s.book Seite 29 Montag, 15. August 2016 1:50 13