48
cassette type air conditioners, Montaro II series
< 500mm
< 1200mm
For four-way cassette units:
Material Diameter, mm Distance between prop stands, m
PVC 25 - 40 1,5 - 2
The diameter of drainpipe should meet the drainage requirement at least. The
dimension of drainpipe can’t less than the connecting dimension of indoor drainpipe.
The drainpipe should be heat-insulated to prevent condensation.
If the pressure at the connection of the drainpipe is negative, it needs to design
drainpipe trap (Fig. 7.3.6.(c)). Every indoor unit needs one drainpipe trap. A plug should
be designed to do cleaning.
It is allowed to use one drainage system for some indoor units (Fig. 7.3.6. (d)).
Indoor unit with drain pump and indoor unit without drain pump should be in different
drainage system.
Fig. 7.3.6.(b)
Fig. 7.3.6.(c)
Fig. 7.3.6.(d)