Castel MAC HC 40 NTV [12/18] Defrosting management
![Castel MAC HC 40 NTV [12/18] Defrosting management](/views2/1318627/page12/bgc.png)
12
GB
5.1 Manual defrosting
(not available for HC20 BT - BT/2 - NT - NT/2)
It is possible to activate manual defrosting:
press the MENU button move to MENU4
DEFROSTING with buttons
or and
press the
ENTER
button.
The controller requests a further confirmation, dis-
playing EXIT or CONFIRM.
Press the button to confirm or the
ENTER
button to exit and return to the initial mask.
Message with active defrosting:
At the end of the defrosting the compressor starts
again and the display will show the
wording RECOVERY until the set-point tempera-
ture is reached.
The defrosting can terminate on reaching the
defrosting setpoint detected by the two sensors
on the evaporator or because a maximum defrost-
ing time has been reached. If the maximum tem-
perature is reached, the controller signals the fault
with the following flashing alarm message and
buzzer:
The controller memorises the type of alarm, date
and time.
To cancel the alarm message, press the
ENTER
button.
The alarm is anyway registered in the controller’s
alarm log.
5.2 Periodic defrosting
(not available for HC20 BT - BT/2 - NT - NT/2)
For all models, the defrosting must be repeated
automatically and at regular intervals starting
immediately after the instrument comes on.
The time elapsing between one automatic defrost-
ing and the next is set in the factory at six hours.
In this case too, the defrosting can terminate
when the end of defrosting temperature detected
by the two sensors on the evaporator is reached
or because a maximum defrosting time has been
reached.
The fault is shown as in the case of manual
defrosting.
5.3 Timed defrosting
(not available for HC20 BT - BT/2 - NT - NT/2)
It is possible to set the start time of four automat-
ic defrostings a day that are always repeated over
the twenty-four hour period. In this way, the auto-
matic periodic defrostings are inhibited.
The defrosting term occurs in the way described
previously.
F18 DEFR. TIME
S 19/02/02 06:09
DEFR. TIME
—> Call SERVICE
RECOVERY >>OK
CELL -10,5°C
DEFROS >>OK
CELL -18°C
Menu 4
DEFROSTING
5. DEFROSTING MANAGEMENT
Содержание
- Conservation cabinets 1
- Highcontrol 1
- Instructions for use 1
- General documentation 4
- General information 4
- Out fig for the stainless steel versions wear protective gloves when han dling the packaging and the wooden base 4
- Installation 5
- Accessories 8
- Hc 20 c nt ntv ntb btv fx 8
- Hc 20 nt 2 bt 2 btv 2 8
- Hc 40 btv ntb ntv 8
- Operating spaces 8
- Positioning 8
- Technical characteristics 9
- Date 12 04 03 time 11 54 23 11
- Hc20nt 2 hc20ntv hc20btv hc20btv 2 hc40ntv hc40btv 11
- Menu 2 change setpoint 11
- New set 15 c current 15 c 11
- Ok cell 21 c 11
- Call service 12
- Defrosting management 12
- F18 defr time s 19 02 02 06 09 12
- Menu 4 defrosting 12
- Ok cell 10 5 c 12
- Ok cell 18 c 12
- Al 27 high temp duration 015 13
- Al 27 high temp max temp 25 c 13
- Al 27 high temp s 18 03 02 12 29 13
- Alarm detected cell 24 0 c 13
- Ht cell 18 c 13
- Lt cell 24 c 13
- Management of the alarms detected and turning them off 13
- Al 26 black out b 15 03 02 10 22 14
- Al 26 black out max temp 12 c 14
- Al 26 black out s 15 03 02 10 01 14
- Alarm detected cell 24 0 c 14
- Button the cancellation is automatic when the mal function is rectified the alarm is however logged in the alarm menu 14
- Contact an authorised tecnomac centre in the case of a serious alarm 14
- Example of a blackout alarm 14
- Important 14
- In the case of high low temperature alarms before being registered a prealarm time of sixty minutes is calculated at the end of this time the controller logs the alarm in the alarm log and shows the following mask on the display 14
- Malfunctioning message they jeopardise machine operation call the service message display cause cancellation 14
- Serious alarm list serious alarms can determine the incorrect functioning of the conservator the display is the same as that described for the alarms and the signalling buzzer is acti vated to silence the buzzer press the 14
- To eliminate the indication go into the alarm log as shown in the paragraph above 14
- Alarm detected fixed logging of a remove the cause of the alarm alarm in the log and enter into menu 1 alarm log to reset the controller 15
- Ht fixed high temp prealarm automatic rectification 15
- List of any other malfunctions that cannot be signalled 15
- Lt fixed low temp prealarm automatic rectification 15
- Set clock loss of clock data set clock data 15
- Signalling messages they do not jeopardise the functioning of the machine message display cause cancellation 15
- Ordinary maintenance 16
Похожие устройства
- Castel MAC TC 60 N Инструкция по эксплуатации
- Castel MAC HC 20 BT Инструкция по эксплуатации
- Castel MAC HC 20 NTB Инструкция по эксплуатации
- Steno PL7B Инструкция по эксплуатации
- ТОРГМАШ УКМ-14 Инструкция по эксплуатации
- ТОРГМАШ УКМ-14 Сертификат
- ТОРГМАШ УКМ-14 Каталог оборудования ТОРГМАШ
- Pavoni MINITEMPER Инструкция по эксплуатации
- Pavoni MINITEMPER Каталог оборудования Pavoni (англ.)
- Castel MAC HC 20 C Инструкция по эксплуатации
- Talsa Н26pa Инструкция по эксплуатации
- Talsa H42pas Инструкция по эксплуатации
- Talsa Н31pas Инструкция по эксплуатации
- Talsa Н15pa Инструкция по эксплуатации
- Helia Smoker 48 Инструкция по эксплуатации
- Helia Smoker 48 Рецепты копчения
- Helia Smoker 24 Инструкция по эксплуатации
- Helia Smoker 24 Рецепты копчения
- CAS CNW-460 Инструкция по эксплуатации
- CAS СNW-520 Инструкция по эксплуатации