6
GB
(fig. 1)
If the appliances are not perfectly level,
their correct operation and condensate
run-off may be compromised.
AVOID
direct exposure to sunlight
closed sites with high temperatures and
poor air circulation
Do not install the appliance near any heat
sources (fig. 4).
2.3 Ambient temperature and
air circulation
For air-cooled refrigerating units, the
maximum ambient temperature for ope-
ration is 32°C. Correct operation cannot
be guaranteed at higher temperatures.
The appliance can operate safely up to
38°C.
Remote condensing units must be instal-
led in special rooms or outdoors, in a
place protected against direct sunlight; if
necessary the installer must evaluate the
use of a covering or roof structure (the
costs are borne by the purchaser).
In any case, sufficient air interchange
must be guaranteed.
2.4 Electrical connections
A differential thermal-magnetic circuit
breaker complete with disconnecting
switch must be installed ahead of every
appliance, in accordance with current
regulations in the country of installation.
Electrical connection cables must com-
ply with the characteristics given in the
technical data (see appliance wiring dia-
grams, the installer’s responsibility)
The earth wire must be correctly connec-
ted to an efficient earthing system.
THE MANUFACTURER DECLINES ALL
LIABILITY AND WARRANTY OBLIGA-
TIONS IN THE EVENT OF INJURY TO
PERSONS OR DAMAGE TO EQUIP-
MENT AND THINGS, DUE TO INCOR-
RECT INSTALLATION AND/OR FAILU-
RE TO COMPLY WITH CURRENT
LAWS.
2.5 Connection of refrigerator-remote
units
Appliance feed lines are sized for instal-
lation distances of up to 10 metres. For
greater distances, contact Castelmac.
2.6 Condensate drainage connection
For all models, fit a condensate/wash
water drainage hose with a minimum dia-
meter of 1” (“geberit” type or similar).
2.7 Information for the installer
Before starting up the machine, check
that it has been correctly installed and
commissioned (test report)
1. Make sure there are no gas leaks from
welds or joints made during the installa-
tion phase.
2. Check that the pipes connecting the con-
denser to the remote condensing unit
have been well insulated.