Mitsubishi Electric PKA-RP50HAL / PUHZ-ZRP50VHA [2/36] Safety precautions
![Mitsubishi Electric PKA-RP50HAL / PUHZ-ZRP50VHA [2/36] Safety precautions](/views2/1330958/page2/bg2.png)
2
5. Drainage piping work .........................................................................................7
6. Electrical work ...................................................................................................8
7. Test run ............................................................................................................14
8. Easy maintenance function .............................................................................18
► Before installing the unit, make sure you read all the “Safety
precautions”.
► Please report to your supply authority or obtain their consent before
connecting this equipment to the power supply system.
Warning:
Describes precautions that must be observed to prevent danger of injury or
death to the user.
Caution:
Describes precautions that must be observed to prevent damage to the unit.
Contents
Warning:
• Ask a dealer or an authorized technician to install the unit.
• For installation work, follow the instructions in the Installation Manual and use
tools and pipe components specifically made for use with refrigerant specified
in the outdoor unit installation manual.
• The unit must be installed according to the instructions in order to minimize
the risk of damage from earthquakes, typhoons, or strong winds. An
incorrectly installed unit may fall down and cause damage or injuries.
• The unit must be securely installed on a structure that can sustain its
weight.
• If the air conditioner is installed in a small room, measures must be taken to
prevent the refrigerant concentration in the room from exceeding the safety
limit in the event of refrigerant leakage. Should the refrigerant leak and cause
the concentration limit to be exceeded, hazards due to lack of oxygen in the
room may result.
• Ventilate the room if refrigerant leaks during operation. If refrigerant comes
into contact with a flame, poisonous gases will be released.
• All electric work must be performed by a qualified technician according to
local regulations and the instructions given in this manual.
• Use only specified cables for wiring. The wiring connections must be made
securely with no tension applied on the terminal connections. Also, never
splice the cables for wiring (unless otherwise indicated in this document).
Failure to observe these instructions may result in overheating or a fire.
• The appliance shall be installed in accordance with national wiring
regulations.
• The terminal block cover panel of the unit must be firmly attached.
• If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent or similarly qualified persons in order to avoid a hazard.
• Use only accessories authorized by Mitsubishi Electric and ask a dealer or
an authorized technician to install them.
• The user should never attempt to repair the unit or transfer it to another
location.
• After installation has been completed, check for refrigerant leaks. If refrigerant
leaks into the room and comes into contact with the flame of a heater or
portable cooking range, poisonous gases will be released.
• When installing or relocating, or servicing the air conditioner, use only the
specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it
with any other refrigerant and do not allow air to remain in the lines.
If air is mixed with the refrigerant, then it can be the cause of abnormal high
pressure in the refrigerant line, and may result in an explosion and other
hazards.
The use of any refrigerant other than that specified for the system will cause
mechanical failure or system malfunction or unit breakdown. In the worst
case, this could lead to a serious impediment to securing product safety.
1.1. Before installation (Environment)
Caution:
• Do not use the unit in an unusual environment. If the air conditioner is
installed in areas exposed to steam, volatile oil (including machine oil), or
sulfuric gas, areas exposed to high salt content such as the seaside, the
performance can be significantly reduced and the internal parts can be
damaged.
• Do not install the unit where combustible gases may leak, be produced,
flow, or accumulate. If combustible gas accumulates around the unit, fire
or explosion may result.
• Do not keep food, plants, caged pets, artwork, or precision instruments in
the direct airflow of the indoor unit or too close to the unit as these items
can be damaged by temperature changes or dripping water.
• When the room humidity exceeds 80% or when the drainpipe is clogged,
water may drip from the indoor unit. Do not install the indoor unit where
such dripping can cause damage.
• When installing the unit in a hospital or communications office, be
prepared for noise and electronic interference. Inverters, home appliances,
high-frequency medical equipment, and radio communications equipment
can cause the air conditioner to malfunction or breakdown. The air
conditioner may also affect medical equipment, disturbing medical care,
and communications equipment, harming the screen display quality.
1. Safety precautions
After installation work has been completed, explain the “Safety precautions,” use,
and maintenance of the unit to the customer according to the information in the
Operation Manual and perform the test run to ensure normal operation. Both the
Installation Manual and Operation Manual must be given to the user for keeping.
These manuals must be passed on to subsequent users.
: Indicates a part which must be grounded.
Warning:
Carefully read the labels affixed to the main unit.
1.4. Before starting the test run
Caution:
• Turn on the main power switch more than 12 hours before starting operation.
Starting operation just after turning on the power switch can severely damage
the internal parts.
• Before starting operation, check that all panels, guards and other protective
parts are correctly installed. Rotating, hot, or high voltage parts can cause
injuries.
• Do not operate the air conditioner without the air filter set in place. If the air
filter is not installed, dust may accumulate and breakdown may result.
• Do not touch any switch with wet hands. Electric shock may result.
• Do not touch the refrigerant pipes with bare hands during operation.
• After stopping operation, be sure to wait at least five minutes before turning
off the main power switch. Otherwise, water leakage or breakdown may
result.
1.3. Before electric work
Caution:
• Be sure to install molded case circuit breakers. If not installed, electric shock
may result.
• For the power lines, use standard cables of sufficient capacity. Otherwise, a
short circuit, overheating, or fire may result.
• When installing the power lines, do not apply tension to the cables.
• Be sure to ground the unit. If the unit is not properly grounded, electric shock
may result.
• Use circuit breakers (ground fault interrupter, isolating switch (+B fuse),
and molded case circuit breaker) with the specified capacity. If the circuit
breaker capacity is larger than the specified capacity, breakdown or fire may
result.
1.2. Before installation or relocation
Caution:
• Be extremely careful when transporting the units. Two or more persons
are needed to handle the unit as it weighs 20 kg or more. Do not grasp the
packaging bands. Wear protective gloves as you can injure your hands on
the fins or other parts.
• Be sure to safely dispose of the packaging materials. Packaging materials,
such as nails and other metal or wooden parts may cause stabs or other
injuries.
• Thermal insulation of the refrigerant pipe is necessary to prevent condensation.
If the refrigerant pipe is not properly insulated, condensation will be formed.
• Place thermal insulation on the pipes to prevent condensation. If the
drainpipe is installed incorrectly, water leakage and damage to the ceiling,
floor, furniture, or other possessions may result.
• Do not clean the air conditioner unit with water. Electric shock may result.
• Tighten all flare nuts to specification using a torque wrench. If tightened
too much, the flare nut can break after an extended period.
1. Safety precautions .............................................................................................2
2. Installation location ............................................................................................3
3. Installing the indoor unit ....................................................................................3
4. Installing the refrigerant piping ..........................................................................6
Note:
The phrase “Wired remote controller” in this installation manual refers to the PAR-31MAA.
If you need any information for the other remote controller, please refer to either the installation manual or initial setting manual which are
included in these boxes.
Содержание
- Air conditioners кондиционеры 1
- Deutsch 1
- English 1
- Español 1
- Eγxeipiδio oδhγiωn eγkataσtaσhσ 1
- Français 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Installationsmanual 1
- Italiano 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands 1
- Pka rp hal 1
- Português 1
- Svenska 1
- Türkçe 1
- Ελληνικά 1
- Руководство по установке 1
- Русский 1
- Before electric work 2
- Before installation environment 2
- Before installation or relocation 2
- Before starting the test run 2
- Contents 2
- Note the phrase wired remote controller in this installation manual refers to the par 31maa if you need any information for the other remote controller please refer to either the installation manual or initial setting manual which are included in these boxes 2
- Safety precautions 2
- Check the indoor unit accessories fig 3 1 3
- Fig 2 1 3
- Fig 3 1 3
- Fig 3 2 3
- Fig 3 3 3
- Installation location 3
- Installing the indoor unit 3
- Installing the wall mounting fixture fig 3 2 3
- Outline dimensions indoor unit fig 2 1 3
- Extraction and processing of the piping and wiring fig 3 6 4
- Fig 3 4 4
- Fig 3 5 4
- Fig 3 6 4
- Fig 3 7 4
- Installing the indoor unit 4
- Installing the wall mounting fixture 4
- Pka rp hal 4
- Pka rp hal fig 3 4 4
- Preparing the indoor unit 4
- Rear right and lower piping fig 3 7 4
- When embedding pipes into the wall fig 3 5 4
- Fig 3 10 5
- Fig 3 11 5
- Fig 3 8 5
- Fig 3 9 5
- Installing the indoor unit 5
- Left and left rear piping fig 3 11 5
- Left and left rear piping fig 3 8 5
- Mounting the indoor unit 5
- Pka rp hal 5
- Rear right and lower piping fig 3 9 5
- Connecting pipes fig 4 1 6
- Fig 4 1 6
- Fig 4 2 6
- Fig 4 3 6
- Indoor unit 6
- Installing the refrigerant piping 6
- Positioning refrigerant and drain piping fig 4 2 6
- Refrigerant piping fig 4 3 6
- Check of drainage fig 5 4 7
- Drainage piping work 7
- Drainage piping work fig 5 1 7
- Fig 4 4 7
- Fig 5 1 7
- Fig 5 2 7
- Fig 5 3 7
- Fig 5 4 7
- Installing the refrigerant piping 7
- Preparing left and left rear piping fig 5 2 7
- Storing in the piping space of the indoor unit fig 5 3 7
- Storing in the piping space of the unit fig 4 7
- 1 system 8
- Electrical work 8
- Fig 6 1 8
- Indoor unit 8
- Indoor unit power supplied from outdoor unit 8
- Pka rp hal 8
- Pka rp hal fig 6 1 8
- Simultaneous twin triple four system 8
- 1 system 9
- Affix a label b that is included with the manuals near each wiring diagram for the indoor and outdoor units 9
- Electrical work 9
- Notes 1 wiring size must comply with the applicable local and national code 2 power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord design 60245 iec 57 3 install an earth longer than other cords 9
- Separate indoor unit outdoor unit power supplies for puhz application only 9
- Simultaneous twin triple four system 9
- The following connection patterns are available the outdoor unit power supply patterns vary on models 9
- The optional wiring replacement kit is required 9
- The optional wiring replacement kits are required 9
- Electrical work 10
- If the indoor and outdoor units have separate power supplies refer to the table at the below if the optional wiring replacement kit is used change the indoor unit electrical box wiring refering to the figure in the right and the dip switch settings of the outdoor unit control board 10
- Indoor unit specifications indoor power supply terminal kit option required indoor unit electrical box connector connection change required 10
- Label affixed near each wiring diagram for the indoor and outdoor units required 10
- Never splice the power cable or the indoor outdoor connection cable otherwise it may result in a smoke a fi re or communication failure 10
- Notes 1 wiring size must comply with the applicable local and national code 2 power supply cords and indoor unit outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord design 60245 iec 57 3 install an earth longer than other cables 10
- On off 1 2 sw8 3 10
- Outdoor unit dip switch settings when using separate indoor unit outdoor unit power supplies only 10
- There are three types of labels labels a b and c affix the appropriate labels to the units according to the wiring method 10
- Warning 10
- Assigning a remote controller to each unit fig 6 4 11
- Electrical work 11
- Fig 6 2 11
- Fig 6 3 11
- Fig 6 4 11
- For wired remote controller 1 two remote controllers setting 11
- For wireless remote controller 1 installation area 11
- Installation method fig 6 2 11
- Remote controller 11
- Setting fig 6 3 11
- Wireless remote controller pair number setting operation 11
- Electrical work 12
- Fig 6 5 fig 6 6 12
- Fig 6 7 fig 6 8 12
- Fig 6 9 12
- Function setting on the unit selecting the unit functions 12
- Function settings 12
- Electrical work 13
- Fig 6 10 13
- For wireless remote controller fig 6 10 13
- Function setting on the remote controller 13
- Function table 13
- Before test run 14
- Fig 7 1 14
- Fig 7 2 14
- Fig 7 3 14
- Fig 7 4 14
- Insulation resistance 14
- Test run 14
- Using wired remote controller 14
- Fig 7 5 15
- Fig 7 6 15
- Self check 15
- Test run 15
- Using sw4 in outdoor unit 15
- Using wireless remote controller fig 7 5 15
- Wired remote controller 15
- Wireless remote controller fig 7 6 15
- Test run 16
- Test run 17
- Easy maintenance function 18
- F1 f2 f3 f4 18
- Меры предосторожности 19
- Перед тестовым прогоном 19
- Перед установкой или перемещением 19
- Перед установкой окружающая среда 19
- Перед электрическими работами 19
- Содержание 19
- Количество 20
- Контурные габариты внутренний прибор рис 2 1 20
- Место установки 20
- Проверьте наличие дополнительных принадлежностей к внутреннему прибору рис 3 1 20
- Рис 2 1 20
- Рис 3 1 20
- Рис 3 2 рис 3 3 20
- Установка внутреннего прибора 20
- Установка настенного крепления рис 3 2 20
- Pka rp hal 21
- Pka rp hal рис 3 4 21
- Встраивание труб в стены рис 3 5 21
- Извлечение и обработка трубопроводов и электропроводки рис 3 6 21
- Подготовка внутреннего блока 21
- Правые левые и нижние трубопроводы рис 3 7 21
- Рис 3 4 21
- Рис 3 5 21
- Рис 3 6 21
- Рис 3 7 21
- Установка внутреннего прибора 21
- Установка настенного кронштейна 21
- Pka rp hal 22
- Левая и левая нижняя трубки рис 3 11 22
- Левая и левая нижняя трубки рис 3 8 22
- Правые левые и нижние трубопроводы рис 3 9 22
- Рис 3 10 22
- Рис 3 11 22
- Рис 3 8 22
- Рис 3 9 22
- Установка внутреннего блока 22
- Установка внутреннего прибора 22
- Внутренний блок 23
- Выбор расположения труб хладагента и дренажных труб рис 4 2 23
- Прокладка труб хладагента 23
- Рис 4 1 23
- Рис 4 2 23
- Рис 4 3 23
- Соединение труб рис 4 1 23
- Трубы хладагента рис 4 3 23
- Дренажные трубы 24
- Дренажные трубы рис 5 1 24
- Подготовка труб слева и слева сзади рис 5 2 24
- Проверка дренажа рис 5 4 24
- Прокладка труб хладагента 24
- Рис 4 4 24
- Рис 5 1 24
- Рис 5 2 24
- Рис 5 3 24
- Рис 5 4 24
- Укладка в место для трубок блока рис 4 4 24
- Укладка в место для трубок внутреннего блока рис 5 3 24
- Pka rp hal 25
- Pka rp hal рис 6 1 25
- Внутренний блок 25
- Одновременная двойная тройная четверная система 25
- Питание на внутренний прибор подается от наружного прибора 25
- Рис 6 1 25
- Система 1 1 25
- Электрические работы 25
- Имеются следующие шаблоны подключения конструкция блока питания внешнего прибора зависит от модели 26
- Одновременная двойная тройная четверная система 26
- Отдельные источники электропитания для внутреннего прибора наружного прибора только для применения puhz 26
- Прикрепите бирку b прилагаемую к руководствам около каждой схемы подключения для внутреннего и наружного приборов 26
- Примечания 1 диаметр проводов должен соответствовать применимым местным и национальным нормам 2 силовые кабели и кабели соединения внутреннего наружного прибора не должны быть легче экранированного гибкого провода из полихлоропрена модель 60245 iec 57 3 длина устанавливаемого кабеля заземления должна превышать длину других кабелей 26
- Система 1 1 26
- Требуется дополнительный сменный комплект проводки 26
- Требуются дополнительные комплекты для замены проводов 26
- Электрические работы 26
- On off 1 2 sw8 3 27
- Бирка прикрепленная около каждой схемы подключения для внутреннего и наружного приборов требуется 27
- Если у внутреннего и наружного приборов различные источники электропитания см таблицу ниже если используется дополнительный сменный комплект проводки измените проводку распределительной коробки внутреннего прибора в соответствии с рисунком справа и настройки микропереключателя панели управления наружного прибора 27
- Изменение соединения разъема распределительной коробки внутреннего прибора требуется 27
- Имеется три типа бирок бирки a b и c прикрепите соответствующие бирки к блокам в соответствии с методом подключения проводки 27
- Настройка микропереключателя наружного прибора только при использовании отдельных источников электропитания для внутреннего прибора наружного прибора 27
- Никогда не подсоединяйте внахлест силовой кабель или соединительный кабель внешнего питания это может привести к задымлению возгоранию или неисправности 27
- Предупреждение 27
- Примечания 1 диаметр проводов должен соответствовать применимым местным и национальным нормам 2 силовые кабели и кабели соединения внутреннего наружного прибора не должны быть легче экранированного гибкого провода из полихлоропрена модель 60245 iec 57 3 длина устанавливаемого кабеля заземления должна превышать длину других кабелей 27
- Спецификации внутреннего прибора комплект клемм источника электропитания внутреннего прибора дополнительно требуется 27
- Электрические работы 27
- Для беспроводного пульта дистанционного управления 1 места установки 28
- Метод установки рис 6 2 28
- Настройка двух пультов дистанционного управления 28
- Настройка рис 6 3 28
- Приписание пульта дистанционного управления отдельным приборам рис 6 4 28
- Процедура настройки номера пары пульта дистанционного управления 28
- Пульт дистанционного управления 28
- Рис 6 2 28
- Рис 6 3 28
- Рис 6 4 28
- Электрические работы 28
- Рис 6 5 рис 6 6 29
- Рис 6 7 рис 6 8 29
- Рис 6 9 29
- Установки функций 29
- Функциональная настройка прибора выбор функций прибора 1 для проводного пульта дистанционного управления 29
- Электрические работы 29
- Для беспроводного пульта дистанционного управления рис 6 10 30
- Рис 6 10 30
- Таблица функций 30
- Функциональная настройка на пульте дистанционного управления 30
- Электрические работы 30
- Выполнение испытания 31
- Перед пробным прогоном 31
- Рис 7 1 31
- Рис 7 2 31
- Рис 7 3 31
- Рис 7 4 31
- Сопротивление изоляции 31
- Выполнение испытания 32
- Для беспроводного пульта дистанционного управления рис 7 6 32
- Для проводного пульта дистанционного управления 32
- Использование sw4 в наружном блоке 32
- Использование беспроводного пульта дистанционного управления рис 7 5 32
- Рис 7 5 32
- Рис 7 6 32
- Самодиагностика 32
- Выполнение испытания 33
- Выполнение испытания 34
- F1 f2 f3 f4 35
- Функция простого техобслуживания 35
Похожие устройства
- Mitsubishi Electric PKA-RP50HAL / PUHZ-ZRP50VHA Руководство по установке
- Mitsubishi Electric PKA-RP50HAL / PUHZ-ZRP50VHA Сертификат
- Mitsubishi Electric PKA-RP60KAL / PUHZ-ZRP60VHA Инструкция по эксплуатации
- Mitsubishi Electric PKA-RP60KAL / PUHZ-ZRP60VHA Руководство по установке
- Mitsubishi Electric PKA-RP60KAL / PUHZ-ZRP60VHA Сертификат
- Mitsubishi Electric PKA-RP100KAL / PUHZ-SHW112VHA Инструкция по эксплуатации
- Mitsubishi Electric PKA-RP100KAL / PUHZ-SHW112VHA Руководство по установке
- Mitsubishi Electric PKA-RP100KAL / PUHZ-SHW112VHA Сертификат
- Mitsubishi Electric PKA-RP71KAL / PUHZ-ZRP71VHA Инструкция по эксплуатации
- Mitsubishi Electric PKA-RP71KAL / PUHZ-ZRP71VHA Руководство по установке
- Mitsubishi Electric PKA-RP71KAL / PUHZ-ZRP71VHA Сертификат
- Mitsubishi Electric MSZ-EF50VEW Инструкция по эксплуатации
- Mitsubishi Electric MSZ-EF50VEW Руководство по установке
- Mitsubishi Electric MSZ-EF50VEW Сертификат
- Mitsubishi Electric PKA-RP100KAL / PUHZ-ZRP100YKA Инструкция по эксплуатации
- Mitsubishi Electric PKA-RP100KAL / PUHZ-ZRP100YKA Руководство по установке
- Mitsubishi Electric PKA-RP100KAL / PUHZ-ZRP100YKA Сертификат
- Mitsubishi Electric PKA-RP100KAL / PUHZ-P100VHA Инструкция по эксплуатации
- Mitsubishi Electric PKA-RP100KAL / PUHZ-P100VHA Руководство по установке
- Mitsubishi Electric PKA-RP100KAL / PUHZ-P100VHA Сертификат