Mitsubishi Electric PUHY-EP450YLM-A [32/56] 9 additional refrigerant charge

Mitsubishi Electric PUHY-EP450YLM-A [32/56] 9 additional refrigerant charge
GB-30
WT07281X03
9-9. Additional refrigerant charge
Charge refrigerant in a liquid state.
- Charging refrigerant in the gaseous state will change the composition of the refrigerant and lead
to a performance drop.
Do not use a charging cylinder when charging refrigerant.
- The use of a charging cylinder may change the composition of the refrigerant and lead to a
performance drop.
The amount of refrigerant that is shown in the table below is factory-charged in the outdoor units. The amount
necessary for extended piping is not included and needs to be added on site.
Unit model Factory-charged amount [kg (oz)] Unit model Factory-charged amount [kg (oz)]
EP200 7.5 (265) EP400 11.8 (417)
EP250 7.5 (265) EP450 11.8 (417)
EP300 10.3 (364) EP500 11.8 (417)
EP350 10.3 (364)
The amount of refrigerant that is shown in the table below is the maximum amount to be added on site.
Unit model Maximum amount to be added [kg (oz)] Unit model Maximum amount to be added [kg (oz)]
EP200YLM 22.3 (786) EP500YSLM 47.0 (1659)
EP250YLM 29.7 (1048) EP550YSLM 51.3 (1811)
EP300YLM 32.7 (1152) EP600YSLM 53.9 (1900)
EP350YLM 33.6 (1184) EP650YSLM 56.5 (1992)
EP400YLM 37.2 (1311) EP700YSLM 68.9 (2430)
EP450YLM 45.0 (1589) EP750YSLM 68.9 (2430)
EP500YLM 45.9 (1621) EP800YSLM 71.4 (2519)
EP850YSLM 73.2 (2583)
EP900YSLM 75.7 (2671)
EP950YSLM 75.7 (2671)
EP1000YSLM 80.7 (2846)
EP1050YSLM 80.7 (2846)
EP1100YSLM 80.7 (2846)
EP1150YSLM 80.7 (2846)
EP1200YSLM 83.8 (2957)
EP1250YSLM 83.8 (2957)
EP1300YSLM 87.0 (3068)
EP1350YSLM 87.0 (3068)
Both refrigerant overcharge and undercharge will cause problems. Charge the system with the proper amount of
refrigerant.
Record the added refrigerant amount on the label attached to the control box panel for future servicing.
9-9-1. Calculation of the amount of additional refrigerant
The amount of refrigerant to be added depends on the size and the total length of the liquid piping.
Calculate the amount of refrigerant to be charged according to the formula below.
Round up the calculation result to the nearest 0.1 kg (0.1 oz).