Mitsubishi Electric PLFY-P32VBM-E [4/28] Installing the indoor unit
![Mitsubishi Electric PLFY-P100VBM-E [4/28] Installing the indoor unit](/views2/1331640/page4/bg4.png)
4
GB
17
105
(
240
)
+5
0
Min. 30
A=17
+5
0
Suspension bolt
Ceiling
Nut
Washer (with insulation)
Mounting plate
Washer (without insulation)
Check using the Installation gauge
Main unit
Ceiling
Installation template (top of the
package)
Screw with washer (Accessory)
Main unit
Ceiling
Gauge
Ceiling opening dimensions
Fig. 2-5
Fig. 2-6
Fig. 2-7
2. Installing the indoor unit
Fig. 3-1
øA
45° ± 2°
Fig. 3-2
2.5. Unit suspension procedures (Fig. 2-5)
Suspend the main unit as shown in the diagram.
Figures given in parentheses represent the dimensions in case of installing optional
multi function casement.
1. In advance, set the parts onto the suspension bolts in the order of the washers
(with insulation), washers (without insulation) and nuts (double).
• Fit the washer with cushion so that the insulation faces downward.
• In case of using upper washers to suspend the main unit, the lower washers (with
insulation) and nuts (double) are to be set later.
2. Lift the unit to the proper height of the suspension bolts to insert the mounting
plate between washers and then fasten it securely.
3. When the main unit can not be aligned against the mounting hole on the ceiling,
it is adjustable owing to a slot provided on the mounting plate.
• Make sure that A is performed within 17-22 mm. Damage could result by failing
to adhere to this range. (Fig. 2-6)
Caution:
Use the top half of the box as a protective cover to prevent dust or debris
from getting inside the unit prior to installation of the decorative cover or
when applying ceiling materials.
2.6. Confirming the position of main unit and tighten-
ing the suspension bolts (Fig. 2-7)
• Using the gauge attached to the grille, ensure that the bottom of the main unit is
properly aligned with the opening of the ceiling. Be sure to confirm this, otherwise
condensation may form and drip due to air leakage, etc.
• Confirm that the main unit is horizontally levelled, using a level or a vinyl tube
filled with water.
• After checking the position of the main unit, tighten the nuts of the suspension
bolts securely to fasten the main unit.
• The installation template (top of the package) can be used as a protective sheet
to prevent dust from entering the main unit when the grilles are left unattached for
a while or when the ceiling materials are to be lined after installation of the unit is
finished.
* As for the details of fitting, refer to the instructions given on the Installation tem
-
plate.
3. Refrigerant pipe and drain pipe
24
90
A
B
*
170
*
140
*
190
60
284 377
3.1. Refrigerant and drainage piping locations of
indoor unit
The figure marked with * in the drawing represent the dimensions of the main unit
excluding those of the optional multi function casement. (Fig. 3-1)
Drain pipe
Ceiling
Grille
Refrigerant pipe (liquid)
Refrigerant pipe (gas)
Water supply inlet
Main unit
*
When the optional multi-functional casement is installed, add 135 mm to the
dimensions marked on the figure.
3.2. Connecting pipes (Fig. 3-2)
• When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C or
more, thickness of 12 mm or more).
• The indoor parts of the drain pipe should be wrapped with polyethylene foam in
-
sulation materials (specific gravity of 0.03, thickness of 9 mm or more).
• Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten
-
ing flare nut.
• Use two wrenches to tighten piping connections.
• Use refrigerant piping insulation provided to insulate indoor unit connections. In
-
sulate carefully.
Flare cutting dimensions
Copper pipe O.D.
(mm)
Flare dimensions
øA dimensions (mm)
ø6.35 8.7 - 9.1
ø9.52 12.8 - 13.2
ø12.7 16.2 - 16.6
ø15.88 19.3 - 19.7
ø19.05 22.9 - 23.3
Warning:
When installing the unit, securely connect the refrigerant pipes before start-
ing the compressor.
(mm)
Models A B
20, 25, 32, 40, 50 80 74
63, 80, 100, 125 85 77
90° ± 0.5°
R0.4 - R0.8
Содержание
- Air conditioners for building application indoor unit 1
- Deutsch d 1
- English gb 1
- Español e 1
- Français f 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Italiano i 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands nl 1
- Plfy p vbm e 1
- Português p 1
- Türkçe tr 1
- Εγχειριδιο οδηγιων εγκαταστασησ 1
- Ελληνικά gr 1
- Руководство по установке 1
- Русский ru 1
- Check the indoor unit accessories fig 2 1 2
- Contents 2
- Fig 2 1 2
- Installing the indoor unit 2
- Safety precautions 2
- Branch duct hole and fresh air intake hole fig 2 3 3
- Ceiling openings and suspension bolt installation locations fig 2 2 3
- Fig 2 2 3
- Fig 2 3 3
- Fig 2 4 3
- Installing the indoor unit 3
- Suspension structure give site of suspension strong structure fig 2 4 3
- Connecting pipes fig 3 2 4
- Confirming the position of main unit and tighten ing the suspension bolts fig 2 7 4
- Fig 2 5 4
- Fig 2 6 4
- Fig 2 7 4
- Fig 3 1 4
- Fig 3 2 4
- Installing the indoor unit 4
- Refrigerant and drainage piping locations of indoor unit 4
- Refrigerant pipe and drain pipe 4
- Unit suspension procedures fig 2 5 4
- Drainage piping work fig 3 4 5
- Fig 3 3 5
- Fig 3 4 5
- Fig 3 5 5
- Indoor unit fig 3 3 5
- Refrigerant pipe and drain pipe 5
- Electrical work 6
- Fig 4 1 6
- Fig 4 2 6
- Indoor unit fig 4 1 6
- Power supply wiring 6
- Electrical work 7
- Types of control cables 7
- Connecting remote controller indoor and outdoor transmission cables fig 4 3 8
- Electrical work 8
- Fig 4 3 8
- Fig 4 4 8
- Sensing room temperature with the built in sen sor in a remote controller fig 4 4 8
- Setting addresses fig 4 4 8
- Switch setting for high ceiling or at the time of changing the number of air outlets fig 4 4 8
- Electrical characteristics 9
- Electrical work 9
- How to set the fixed up down air direction only for wired remote controller 9
- Checking the contents fig 5 1 10
- Electrical work 10
- Fig 5 1 10
- Fig 5 2 10
- Installing the grille 10
- Preparing to attach the grille fig 5 2 10
- Fig 5 3 11
- Fig 5 4 11
- Fig 5 5 11
- Fig 5 6 11
- Fig 5 7 11
- Installing the grille 11
- Selection of the air outlets 11
- Fig 5 10 12
- Fig 5 11 12
- Fig 5 8 12
- Fig 5 9 12
- Installation of i see sensor corner panel fig 5 10 12
- Installing the grille 12
- Installing the intake grille fig 5 9 12
- Locking the up down airflow direction fig 5 11 12
- Backlit lcd 13
- Before test run 13
- Controller interface 13
- Fig 6 1 13
- Fig 6 3 fig 6 2 13
- Fig 6 4 13
- Function button f1 13
- Function button f2 13
- Function button f3 13
- Function button f4 13
- Menu button 13
- On off button 13
- On off lamp 13
- Return button 13
- Select button 13
- Test run 13
- Check of drainage fig 6 7 14
- Fig 6 5 14
- Fig 6 6 14
- Fig 6 7 14
- Test run 14
- Fig 2 1 15
- Меры предосторожности 15
- Проверьте наличие дополнительных принадлеж ностей к внутреннему прибору fig 2 1 15
- Содержание 15
- Установка внутреннего прибора 15
- Fig 2 2 16
- Fig 2 3 16
- Fig 2 4 16
- Во время создания входного отверстия для свежего воздуха убедитесь что вы удалили изоляционный материал который наложен на внутренний прибор 16
- Во время установки по мере необходимости используйте отверстия вентиляционного канала вырезанные расположенные в позициях показанных на fig 2 3 16
- Подвесная конструкция обеспечьте прочность на месте подвешивания fig 2 4 16
- При установке ответвлений вентиляционного канала тщательно оберните их изоляцией в противном случае возможно образование конденсации и капание воды 16
- Расположение отверстия в потолке и навесных болтов fig 2 2 16
- Установка внутреннего прибора 16
- Цифры помеченные на рисунке представляют размеры основного прибора не включающие размеры опционального многофункционального оконного перепле та 16
- Fig 2 5 17
- Fig 2 6 17
- Fig 2 7 17
- Fig 3 1 17
- Fig 3 2 17
- Порядок подвешивания прибора fig 2 5 17
- Проверка расположения главного прибора и затягивание навесных болтов fig 2 7 17
- Расположение труб хладагента и дренажных труб для внутреннего блока 17
- Соединение труб fig 3 2 17
- Труба хладагента и дренажная труба 17
- Установка внутреннего прибора 17
- Fig 3 3 18
- Fig 3 4 18
- Fig 3 5 18
- Внутренний прибор fig 3 3 18
- Дренажные трубы fig 3 4 18
- Труба хладагента и дренажная труба 18
- Fig 4 1 19
- Fig 4 2 19
- Внутренний прибор fig 4 1 19
- Электрические работы 19
- Электропроводка для подвода питания 19
- Типы кабелей управления 20
- Электрические работы 20
- Fig 4 3 21
- Fig 4 4 21
- Определение температуры в помещении встро енным датчиком пульта дистанционного управ ления fig 4 4 21
- Подсоединение пульта дистанционного управления кабелей передачи внутри и снаружи fig 4 3 21
- Установка адресов fig 4 4 21
- Установка переключателей при высоком по толке или при именении числа выходов возду ха fig 4 4 21
- Электрические работы 21
- Для изменения направления воздушного потока вверх вниз только для пульта дистанционного управления 22
- Электрические работы 22
- Электрические характеристики 22
- F1 f2 f3 f4 23
- Fig 5 1 23
- Fig 5 2 23
- Подготовка к установке вентиляционной решет ки fig 5 2 23
- Проверка содержимого комплекта fig 5 1 23
- Установка вентиляционной решетки 23
- Электрические работы 23
- Fig 5 3 24
- Fig 5 4 24
- Fig 5 5 24
- Fig 5 6 24
- Fig 5 7 24
- Выбор вытяжных отверстий 24
- Установка вентиляционной решетки 24
- Fig 5 10 25
- Fig 5 11 25
- Fig 5 8 25
- Fig 5 9 25
- Блокировка направления воздушного потока вверх вниз fig 5 11 25
- Проверка 25
- Установка вентиляционной решетки 25
- Установка воздухозаборной решетки fig 5 9 25
- Установка угловой панели i see sensor fig 5 10 25
- Fig 6 1 26
- Fig 6 2 26
- Fig 6 3 26
- Fig 6 4 26
- Выполнение испытания 26
- Индикатор вкл выкл 26
- Интерфейс контроллера 26
- Кнопка вкл выкл 26
- Кнопка возврат 26
- Кнопка выбор 26
- Кнопка меню 26
- Перед пробным прогоном 26
- Подсветка жк экрана 26
- Функциональная кнопка f1 26
- Функциональная кнопка f2 26
- Функциональная кнопка f3 26
- Функциональная кнопка f4 26
- Fig 6 5 27
- Fig 6 6 27
- Fig 6 7 27
- Выполнение испытания 27
- Проверка дренажа fig 6 7 27
Похожие устройства
- Mitsubishi Electric PLFY-P32VBM-E Сертификат
- Mitsubishi Electric PLFY-P32VLMD Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P32VLMD Сертификат
- Mitsubishi Electric PLFY-P40VCM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P40VCM-E Инструкция по установке
- Mitsubishi Electric PLFY-P40VCM-E Сертификат
- Mitsubishi Electric PLFY-P80VBM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P80VBM-E Инструкция по установке
- Mitsubishi Electric PLFY-P80VBM-E Сертификат
- Mitsubishi Electric PLFY-P25VCM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P25VCM-E Инструкция по установке
- Mitsubishi Electric PLFY-P25VCM-E Сертификат
- Mitsubishi Electric PLFY-P40VBM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P40VBM-E Инструкция по установке
- Mitsubishi Electric PLFY-P40VBM-E Сертификат
- Mitsubishi Electric PLFY-P50VBM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P50VBM-E Инструкция по установке
- Mitsubishi Electric PLFY-P50VBM-E Сертификат
- Mitsubishi Electric PLFY-P63VLMD Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P63VLMD Сертификат