Mitsubishi Electric PLFY-P32VBM-E [5/28] Refrigerant pipe and drain pipe
![Mitsubishi Electric PLFY-P40VBM-E [5/28] Refrigerant pipe and drain pipe](/views2/1331640/page5/bg5.png)
5
GB
3.3. Indoor unit (Fig. 3-3)
Heat insulation for refrigerant pipes:
1 Wrap the enclosed large-sized pipe cover around the gas pipe, making sure
that the end of the pipe cover touches the side of the unit.
2 Wrap the enclosed small-sized pipe cover around the liquid pipe, making sure
that the end of the pipe cover touches the side of the unit.
3 Secure both ends of each pipe cover with the enclosed bands. (Attach the
bands 20 mm from the ends of the pipe cover.)
• After connecting the refrigerant piping to the indoor unit, be sure to test the pipe
connections for gas leakage with nitrogen gas. (Check that there is no refrigerant
leakage from the refrigerant piping to the indoor unit.)
Fig. 3-3
3. Refrigerant pipe and drain pipe
3.4. Drainage piping work (Fig. 3-4)
• Use VP25 (O.D. ø32 (1-1/4”) PVC TUBE) for drain piping and provide 1/100 or
more downward slope.
• Be sure to connect the piping joints using a polyvinyl type adhesive.
• Observe the figure for piping work.
• Use the included drain hose to change the extraction direction.
Correct piping
Wrong piping
Insulation (9 mm or more)
Downward slope (1/100 or more)
Support metal
Air bleeder
Raised
Odor trap
Grouped piping
O. D. ø32 PVC TUBE
Make it as large as possible
Indoor unit
Make the piping size large for grouped piping.
Downward slope (1/100 or more)
O. D. ø38 PVC TUBE for grouped piping.
(9 mm or more insulation)
Up to 85 cm
1. Connect the drain socket (supplied with the unit) to the drain port. (Fig. 3-5)
(Fix the tube using PVC adhesive then secure it with a band.)
2. Install a locally purchased drain pipe (PVC pipe, O.D. ø32).
(Fix the pipe using PVC adhesive then secure it with a band.)
3. Insulate the tube and pipe. (PVC pipe, O.D. ø32 and socket)
4. Check that drain flows smoothly.
5. Insulate the drain port with insulating material, then secure the material with a
band. (Both insulating material and band are supplied with the unit.)
Unit
Insulating material
Band (large)
Drain port (transparent)
Insertion margin
Matching
Drain pipe (O.D. ø32 PVC TUBE)
Insulating material (purchased locally)
Transparent PVC pipe
O.D. ø32 PVC TUBE (Slope 1/100 or more)
Band (small)
Drain socket
11
25 25
25
,
Max. 20m
1.5–2m
Max. 15cm
Fig. 3-4
Fig. 3-5
(mm)
Apply refrigerating machine oil over the entire flare seat surface.
* Do not apply refrigerating machine oil to the screw portions.
(This will make the flare nuts more apt to loosen.)
Be certain to use the flare nuts that are attached to the main unit.
(Use of commercially-available products may result in cracking.)
Refrigerant pipe and
insulating material
Pipe cover (large)
Pipe cover (small)
Refrigerant pipe (gas)
Refrigerant pipe (liquid)
Band
Cross-sectional view of
connection
Pipe
Insulating material
Squeeze
Refrigerant pipe sizes & Flare nut tightening torque
R407C or R22 R410A
Flare nut O.D.
Liquid pipe Gas pipe Liquid pipe Gas pipe
Pipe size
(mm)
Tightening
torque
(N.m)
Pipe size
(mm)
Tightening
torque
(N.m)
Pipe size
(mm)
Tightening
torque
(N.m)
Pipe size
(mm)
Tightening
torque
(N.m)
Liquid pipe
(mm)
Gas pipe
(mm)
P20/25/32/40 ODø6.35 (1/4”) 14 - 18 ODø12.7 (1/2”) 49 - 61 ODø6.35 (1/4”) 14 - 18 ODø12.7 (1/2”) 49 - 61 17 26
P50 ODø9.52 (3/8”) 14 - 18* ODø15.88 (5/8”) 49 - 61* ODø6.35 (1/4”) 14 - 18 ODø12.7 (1/2”) 49 - 61 17 26
P63/80 ODø9.52 (3/8”) 34 - 42 ODø15.88 (5/8”) 68 - 82 ODø9.52 (3/8”) 34 - 42 ODø15.88 (5/8”) 68 - 82 22 29
P100/125 ODø9.52 (3/8”) 34 - 42 ODø19.05 (3/4”) 68 - 82* ODø9.52 (3/8”) 34 - 42 ODø15.88 (5/8”) 68 - 82 22 29
* Connect the joint with the following pipes: Liquid and gas pipes of P50, gas pipe of P100/P125.
Содержание
- Air conditioners for building application indoor unit 1
- Deutsch d 1
- English gb 1
- Español e 1
- Français f 1
- Installatiehandleiding 1
- Installation manual 1
- Installationshandbuch 1
- Italiano i 1
- Manual de instalación 1
- Manual de instalação 1
- Manuale di installazione 1
- Manuel d installation 1
- Montaj elki tabi 1
- Nederlands nl 1
- Plfy p vbm e 1
- Português p 1
- Türkçe tr 1
- Εγχειριδιο οδηγιων εγκαταστασησ 1
- Ελληνικά gr 1
- Руководство по установке 1
- Русский ru 1
- Check the indoor unit accessories fig 2 1 2
- Contents 2
- Fig 2 1 2
- Installing the indoor unit 2
- Safety precautions 2
- Branch duct hole and fresh air intake hole fig 2 3 3
- Ceiling openings and suspension bolt installation locations fig 2 2 3
- Fig 2 2 3
- Fig 2 3 3
- Fig 2 4 3
- Installing the indoor unit 3
- Suspension structure give site of suspension strong structure fig 2 4 3
- Connecting pipes fig 3 2 4
- Confirming the position of main unit and tighten ing the suspension bolts fig 2 7 4
- Fig 2 5 4
- Fig 2 6 4
- Fig 2 7 4
- Fig 3 1 4
- Fig 3 2 4
- Installing the indoor unit 4
- Refrigerant and drainage piping locations of indoor unit 4
- Refrigerant pipe and drain pipe 4
- Unit suspension procedures fig 2 5 4
- Drainage piping work fig 3 4 5
- Fig 3 3 5
- Fig 3 4 5
- Fig 3 5 5
- Indoor unit fig 3 3 5
- Refrigerant pipe and drain pipe 5
- Electrical work 6
- Fig 4 1 6
- Fig 4 2 6
- Indoor unit fig 4 1 6
- Power supply wiring 6
- Electrical work 7
- Types of control cables 7
- Connecting remote controller indoor and outdoor transmission cables fig 4 3 8
- Electrical work 8
- Fig 4 3 8
- Fig 4 4 8
- Sensing room temperature with the built in sen sor in a remote controller fig 4 4 8
- Setting addresses fig 4 4 8
- Switch setting for high ceiling or at the time of changing the number of air outlets fig 4 4 8
- Electrical characteristics 9
- Electrical work 9
- How to set the fixed up down air direction only for wired remote controller 9
- Checking the contents fig 5 1 10
- Electrical work 10
- Fig 5 1 10
- Fig 5 2 10
- Installing the grille 10
- Preparing to attach the grille fig 5 2 10
- Fig 5 3 11
- Fig 5 4 11
- Fig 5 5 11
- Fig 5 6 11
- Fig 5 7 11
- Installing the grille 11
- Selection of the air outlets 11
- Fig 5 10 12
- Fig 5 11 12
- Fig 5 8 12
- Fig 5 9 12
- Installation of i see sensor corner panel fig 5 10 12
- Installing the grille 12
- Installing the intake grille fig 5 9 12
- Locking the up down airflow direction fig 5 11 12
- Backlit lcd 13
- Before test run 13
- Controller interface 13
- Fig 6 1 13
- Fig 6 3 fig 6 2 13
- Fig 6 4 13
- Function button f1 13
- Function button f2 13
- Function button f3 13
- Function button f4 13
- Menu button 13
- On off button 13
- On off lamp 13
- Return button 13
- Select button 13
- Test run 13
- Check of drainage fig 6 7 14
- Fig 6 5 14
- Fig 6 6 14
- Fig 6 7 14
- Test run 14
- Fig 2 1 15
- Меры предосторожности 15
- Проверьте наличие дополнительных принадлеж ностей к внутреннему прибору fig 2 1 15
- Содержание 15
- Установка внутреннего прибора 15
- Fig 2 2 16
- Fig 2 3 16
- Fig 2 4 16
- Во время создания входного отверстия для свежего воздуха убедитесь что вы удалили изоляционный материал который наложен на внутренний прибор 16
- Во время установки по мере необходимости используйте отверстия вентиляционного канала вырезанные расположенные в позициях показанных на fig 2 3 16
- Подвесная конструкция обеспечьте прочность на месте подвешивания fig 2 4 16
- При установке ответвлений вентиляционного канала тщательно оберните их изоляцией в противном случае возможно образование конденсации и капание воды 16
- Расположение отверстия в потолке и навесных болтов fig 2 2 16
- Установка внутреннего прибора 16
- Цифры помеченные на рисунке представляют размеры основного прибора не включающие размеры опционального многофункционального оконного перепле та 16
- Fig 2 5 17
- Fig 2 6 17
- Fig 2 7 17
- Fig 3 1 17
- Fig 3 2 17
- Порядок подвешивания прибора fig 2 5 17
- Проверка расположения главного прибора и затягивание навесных болтов fig 2 7 17
- Расположение труб хладагента и дренажных труб для внутреннего блока 17
- Соединение труб fig 3 2 17
- Труба хладагента и дренажная труба 17
- Установка внутреннего прибора 17
- Fig 3 3 18
- Fig 3 4 18
- Fig 3 5 18
- Внутренний прибор fig 3 3 18
- Дренажные трубы fig 3 4 18
- Труба хладагента и дренажная труба 18
- Fig 4 1 19
- Fig 4 2 19
- Внутренний прибор fig 4 1 19
- Электрические работы 19
- Электропроводка для подвода питания 19
- Типы кабелей управления 20
- Электрические работы 20
- Fig 4 3 21
- Fig 4 4 21
- Определение температуры в помещении встро енным датчиком пульта дистанционного управ ления fig 4 4 21
- Подсоединение пульта дистанционного управления кабелей передачи внутри и снаружи fig 4 3 21
- Установка адресов fig 4 4 21
- Установка переключателей при высоком по толке или при именении числа выходов возду ха fig 4 4 21
- Электрические работы 21
- Для изменения направления воздушного потока вверх вниз только для пульта дистанционного управления 22
- Электрические работы 22
- Электрические характеристики 22
- F1 f2 f3 f4 23
- Fig 5 1 23
- Fig 5 2 23
- Подготовка к установке вентиляционной решет ки fig 5 2 23
- Проверка содержимого комплекта fig 5 1 23
- Установка вентиляционной решетки 23
- Электрические работы 23
- Fig 5 3 24
- Fig 5 4 24
- Fig 5 5 24
- Fig 5 6 24
- Fig 5 7 24
- Выбор вытяжных отверстий 24
- Установка вентиляционной решетки 24
- Fig 5 10 25
- Fig 5 11 25
- Fig 5 8 25
- Fig 5 9 25
- Блокировка направления воздушного потока вверх вниз fig 5 11 25
- Проверка 25
- Установка вентиляционной решетки 25
- Установка воздухозаборной решетки fig 5 9 25
- Установка угловой панели i see sensor fig 5 10 25
- Fig 6 1 26
- Fig 6 2 26
- Fig 6 3 26
- Fig 6 4 26
- Выполнение испытания 26
- Индикатор вкл выкл 26
- Интерфейс контроллера 26
- Кнопка вкл выкл 26
- Кнопка возврат 26
- Кнопка выбор 26
- Кнопка меню 26
- Перед пробным прогоном 26
- Подсветка жк экрана 26
- Функциональная кнопка f1 26
- Функциональная кнопка f2 26
- Функциональная кнопка f3 26
- Функциональная кнопка f4 26
- Fig 6 5 27
- Fig 6 6 27
- Fig 6 7 27
- Выполнение испытания 27
- Проверка дренажа fig 6 7 27
Похожие устройства
- Mitsubishi Electric PLFY-P32VBM-E Сертификат
- Mitsubishi Electric PLFY-P32VLMD Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P32VLMD Сертификат
- Mitsubishi Electric PLFY-P40VCM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P40VCM-E Инструкция по установке
- Mitsubishi Electric PLFY-P40VCM-E Сертификат
- Mitsubishi Electric PLFY-P80VBM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P80VBM-E Инструкция по установке
- Mitsubishi Electric PLFY-P80VBM-E Сертификат
- Mitsubishi Electric PLFY-P25VCM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P25VCM-E Инструкция по установке
- Mitsubishi Electric PLFY-P25VCM-E Сертификат
- Mitsubishi Electric PLFY-P40VBM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P40VBM-E Инструкция по установке
- Mitsubishi Electric PLFY-P40VBM-E Сертификат
- Mitsubishi Electric PLFY-P50VBM-E Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P50VBM-E Инструкция по установке
- Mitsubishi Electric PLFY-P50VBM-E Сертификат
- Mitsubishi Electric PLFY-P63VLMD Инструкция по эксплуатации
- Mitsubishi Electric PLFY-P63VLMD Сертификат