Mitsubishi Electric PLFY-P32VBM-E [7/28] Electrical work

Mitsubishi Electric PLFY-P100VBM-E [7/28] Electrical work
7
GB
4.3. Types of control cables
1. Wiring transmission cables
Types of transmission cable Shielding wire CVVS or CPEVS
Cable diameter More than 1.25 mm²
Length Less than 200 m
2. M-NET Remote control cables
Types of remote control cable Shielding wire MVVS
Cable diameter 0.5 to 1.25 mm²
Length
Add any portion in excess of 10 m to within the
longest allowable transmission cable length 200 m
3. MA Remote control cables
Types of remote control cable 2-core cable (unshielded)
Cable diameter 0.3 to 1.25 mm²
Length Less than 200 m
Total operating current of the indoor unit
Minimum wire thickness (mm²)
Ground-fault interrupter *1
Local switch (A)
Breaker for wiring
(NFB)
Main cable Branch Ground Capacity Fuse
F0 = 16 A or less *2 1.5 1.5 1.5 20 A current sensitivity *3 16 16 20
F0 = 25 A or less *2 2.5 2.5 2.5 30 A current sensitivity *3 25 25 30
F0 = 32 A or less *2 4.0 4.0 4.0 40 A current sensitivity *3 32 32 40
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + {V1 × (Quantity of Others)/C}
Indoor unit V1 V2
Type 1 PLFY-VBM, PMFY-VBM, PEFY-VMS,
PCFY-VKM, PKFY-VHM, PKFY-VKM, PLFY-VCM
18.6 2.4
Type 2 PEFY-VMA 38 1.6
Type 3 PEFY-VMHS 13.8 4.8
Others Other indoor unit 0 0
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
*Condition PEFY-VMS × 4 + PEFY-VMA × 1, C = 8 (refer to right sample chart)
F2 = 18.6 × 4/8 + 38 × 1/8
= 14.05
→ 16 A breaker (Tripping current = 8 × 16 A at 0.01s)
*3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type1) + V2 × (Quantity of Type2) + V2 × (Quantity of Type3) + V2 × (Quantity of Others)
+ V3 × (Wire length[km])
G1 Current sensitivity
30 or less 30 mA 0.1sec or less
100 or less 100 mA 0.1sec or less
Wire thickness V3
1.5 mm
2
48
2.5 mm
2
56
4.0 mm
2
66
1 2 3 4 6 8 10 20
C
6000
600
60
10
1
0.1
0.01
SAMPLE
Sample chart
Tripping Time [s]
Rated Tripping current (x)
4. Electrical work

Содержание

Скачать