Toshiba MMU-AP0272H [11/131] 1 cooling heating capacity is based on single connection operation with standard piping length under japanese industrial standard b 8615 condition 1 2 remote controller and ceiling panel are sold separately

Toshiba MMU-AP0272H [11/131] 1 cooling heating capacity is based on single connection operation with standard piping length under japanese industrial standard b 8615 condition 1 2 remote controller and ceiling panel are sold separately
11
Model name
Cooling capacity (*1) kW
Heating capacity (*1) kW
Power supply
Electrical
Running current A
charastaristics
Power consumption kW
Starting current A
Appearance
Height mm
Outer dimension Width mm
Depth mm
Total weight kg
Heat exchanger
Soundproof/Heat-insulating material
Fan
Fan unit Standard air flow (-M -L) m³/h
Motor W
Air filter
Controller (*2)
Connecting pipe
Gas side mm
Liquid side mm
Drain port (Nominal dia. mm)
Sound puressure level High(-Mid.-Low) dB
Model name
Ceiling panel Appearance(Color)
(*2) Outer dimension mm
Total weight kg
Remote controller wiring
(200m or less)
(200m - 500m)
Crossover wiring
(Up to 1000m)
(Up to 2000m)
Spacer for height adjustment
Fresh-air chamber
Option parts Fresh-air inlet box
Air-discharge direction kit
Auxiliary fresh air flange
MMU-AP0362H MMU-AP0482H MMU-AP0562H
11.2 14.0 16.0
12.5 16.0 18.0
1 phase 50Hz 230V (220V-240V) / 1 phase 60Hz 220V
(Separate power supply for indoor units is required.)
0.73 / 0.76 0.88 / 0.92 0.88 / 0.92
0.088 / 0.088 0.112 / 0.112 0.112 / 0.112
0.87 / 0.87 1.23 / 1.23 1.26 / 1.26
Heat-insulating material attached
Zinc hot dipping steel plate
319 319 319
840 840 840
840 840 840
25 25 25
Finned tube
Non-flammable insulation
Turbo fan
1970 (-1430 -1070) 2130 (-1430 -1130) 2130 (-1520 -1230)
68 72 72
Standard filter (Long life filter)
Remote controller
Ø15.9 Ø15.9 Ø15.9
Ø9.5 Ø9.5 Ø9.5
25 (Polyvinyl chloride tube)
43-38-32 46-38-33 46-40-33
RBC-U31PG(W)-E
White (2.5GY9.0/0.5)
Height 30 x Width 950 x Depth 950
4.0
VCTF 0.3mm² (2cores)
VCTF 0.5 to 2.0mm² (2cores)
MVVS (Shield wire) 1.25mm² × 2cores
MVVS (Shield wire) 2.00mm² × 2cores
TCB-SP1602UE TCB-SP1602UE TCB-SP1602UE
TCB-GFC1602UE TCB-GFC1602UE TCB-GFC1602UE
TCB-GB1602UE TCB-GB1602UE TCB-GB1602UE
TCB-BC1602UE TCB-BC1602UE TCB-BC1602UE
TCB-FF101URE2 TCB-FF101URE2 TCB-FF101URE2
(*1) Cooling / heating capacity is based on single connection operation with standard piping length under Japanese
Industrial Standard B 8615 Condition 1.
(*2) Remote controller and ceiling panel are sold separately.

Содержание