Toshiba MMU-AP0272H [9/131] 1 cooling heating capacity is based on single connection operation with standard piping length under japanese industrial standard b 8615 condition 1 2 remote controller and ceiling panel are sold separately

Toshiba MMU-AP0272H [9/131] 1 cooling heating capacity is based on single connection operation with standard piping length under japanese industrial standard b 8615 condition 1 2 remote controller and ceiling panel are sold separately
9
Model name
Cooling capacity (*1) kW
Heating capacity (*1) kW
Power supply
Electrical
Running current A
charastaristics
Power consumption kW
Starting current A
Appearance
Height mm
Outer dimension Width mm
Depth mm
Total weight kg
Heat exchanger
Soundproof/Heat-insulating material
Fan
Fan unit Standard air flow (-M -L) m³/h
Motor W
Air filter
Controller (*2)
Connecting pipe
Gas side mm
Liquid side mm
Drain port (Nominal dia. mm)
Sound puressure level High(-Mid.-Low) dB
Model name
Ceiling panel Appearance (Color)
(*2) Outer dimension mm
Total weight kg
Remote controller wiring
(200m or less)
(200m - 500m)
Crossover wiring
(Up to 1000m)
(Up to 2000m)
Spacer for height adjustment
Fresh-air chamber
Option parts Fresh-air inlet box
Air-discharge direction kit
Auxiliary fresh air flange
MMU-AP0152H MMU-AP0182H
4.5 5.6
5.0 6.3
1phase 50Hz 230V (220V-240V) / 1phase 60Hz 220V
(Separate power supply for indoor units is required.)
0.27 / 0.28 0.29 / 0.30
0.023 / 0.023 0.026 / 0.026
0.33 / 0.33 0.36 / 0.36
Heat-insulating material attached
Zinc hot dipping steel plate
256 256
840 840
840 840
20 20
Finned tube
Non-flammable insulation
Turbo fan
930 (-830 -790) 1050 (-920 -800)
14 14
Standard filter (Long life filter)
Remote controller
Ø12.7 Ø12.7
Ø6.4 Ø6.4
25 (Polyvinyl chloride tube)
31-29-27 32-29-27
RBC-U31PG(W)-E
White (2.5GY9.0/0.5)
Height 30 × Width 950 × Depth 950
4.0
VCTF 0.3mm² (2cores)
VCTF 0.5 to 2.0mm² (2cores)
MVVS (Shield wire) 1.25mm² × 2cores
MVVS (Shield wire) 2.00mm² × 2cores
TCB-SP1602UE TCB-SP1602UE
TCB-GFC1602UE TCB-GFC1602UE
TCB-GB1602UE TCB-GB1602UE
TCB-BC1602UE TCB-BC1602UE
TCB-FF101URE2 TCB-FF101URE2
(*1) Cooling / heating capacity is based on single connection operation with standard piping length under Japanese
Industrial Standard B 8615 Condition 1.
(*2) Remote controller and ceiling panel are sold separately.