5d
High-ceiling adjustment
(Air flow selection)
1-way cassette (SH)
Compact 4-way cassette
Ceiling
0000: Standard
Built-in filter 4-way cassette
0000: Standard filter (factory default)
Ceiling
0000: Standard filter (factory default)
Concealed duct standard
0000: Standard filter (factory default)
0001: High-performance filter (65 %, 90 %)
Static pressure selection Concealed duct standard
0000: Standard (factory default)
0001: High static pressure 1
0003: High static pressure 2
0006: Low static pressure
Slim Duct
0000: Standard (factory default)
0001: High static pressure 1
0003: High static pressure 2
0006: High static pressure 3
60
Timer setting
(wired remote controller)
0000: Available (can be performed) 0001: Unavailable (cannot be
performed)
0000: Available
92
External interlock
release condition
0000: Operation stopped 0001: Release signal received 0000: Operation
stopped
D0
Whether the power
saving mode can be set
by the remote controller
0000: Invalid 0001: Valid 0001: Valid
DN Item Description At shipment
Value Type AP015, AP018 AP024
0000 Standard (factory default) 3.5 m or less 3.8 m or less
0001 High-ceiling (1) 4.0 m or less 4.0 m or less
0003 High-ceiling (3) 4.2 m or less 4.2 m or less
SET
DATA
Type
AP007 to
AP012
AP015 AP018
0000 Standard (factory default) 2.7 m or less 2.9 m or less 3.2 m or less
0002 High-ceiling (2) 3.2 m or less 3.4 m or less
0003 High-ceiling (3) 3.5 m or less 3.5 m or less
Value Type AP015 to AP056
0000 Standard (factory default) 3.5 m or less
0001 High-ceiling (1) 4.0 m or less