Toshiba MMC-AP0244H-E [70/219] Note the same error e g a communication error may result in the display of different check codes depending on the device that detects it moreover check codes detected by the main remote controller central control device do not necessarily have a direct impact on air conditioner operation
69
(Error detected by main remote controller)
(Error detected by central control device)
Note: The same error, e.g. a communication error, may result in the display of different check codes depending on the device that detects it.
Moreover, check codes detected by the main remote controller / central control device do not necessarily have a direct impact on air
conditioner operation.
Check code
Display of receiving unit
Typical fault site Description of error
Main
remote
controller
Outdoor 7-segment display Indicator light block
Sub-code
Flash
E01
No master remote controller,
faulty remote controller
communication (reception)
Signals cannot be received from indoor unit; master remote
controller has not been set (including two remote controller
control).
E02
Faulty remote controller
communication (transmission)
Signals cannot be transmitted to indoor unit.
E09
Duplicated master remote
controller
Both remote controllers have been set as master remote
controller in two remote controller control (alarm and
shutdown for header unit and continued operation for
follower unit)
Check code
Display of receiving unit
Typical fault site Description of error
TCC-LINK
central
control
Outdoor 7-segment display Indicator light block
Sub-code
Flash
C05
No indication (when
main remote controller
also in use)
Faulty central control
communication (transmission)
Central control device is unable to transmit signal due to
duplication of central control device (AI-NET).
C06
Faulty central control
communication (reception)
Central control device is unable to receive signal.
Multiple network adapters
Multiple network adapters are connected to remote
controller communication line (AI-NET).
C12
Blanket alarm for general-
purpose device control
interface
Device connected to general-purpose device control
interface for TCC-LINK / AI-NET is faulty.
P30
As per alarm unit (see
above)
Group control follower unit
error
Group follower unit is faulty (unit No. and above detail [∗∗∗]
displayed on main remote controller)