Toshiba MMC-AP0244H-E [65/219] Target outdoor unit smms shrm mini smms series 1 2

Toshiba MMC-AP0274H-E [65/219] Target outdoor unit smms shrm mini smms series 1 2
64
Target outdoor unit (SMMS, SHRM, Mini-SMMS – Series 1 – 2)
*1 In the case of group connection, only the header indoor unit data can be displayed.
*2 01 ... Only compressor 1 is on
10 ... Only compressor 2 is on
11 ... Both compressor 1 and 2 are on
*3 The upper digit of CODE No. indicates the outdoor unit No.
U1 outdoor unit (Header unit)
U2 outdoor unit (follower unit 1)
U3 outdoor unit (follower unit 2)
U4 outdoor unit (follower unit 3)
CODE No. Data Format Unit Remote controller display example
Indoor unit
data
00 Room temperature (in control) *1 ×1 °C
[0024]=24 °C
01 Room temperature (Remote controller) ×1 °C
02 Air Temperature (TA) ×1 °C
03 Coil Temperature (TCJ) ×1 °C
04 Coil Temperature (TC2) ×1 °C
05 Coil Temperature (TC1) ×1 °C
08 PMV ×1 pls [0050]=500 pls
System
data
0A Number of connected indoor units ×1 [0048]=48
0B Total horse power of connected indoor units ×1 HP [0415]=41.5 HP
0C Number of connected outdoor units ×1 [0004]=4
0D Total horse power of outdoor units ×1 HP [0420]=42 HP
CODE No.
Data Format Unit Remote controller display example
U1 U2 U3 U4
Individual
data 1 of
outdoor
unit *3
10 20 30 40
Discharge temperature of compressor 1
(Td1)
×1 °C
[0024]=24 °C
11 21 31 41
Discharge temperature of compressor 2
(Td2)
×1 °C
12 22 32 42
Detection pressure of high-pressure sensor
(Pd)
×1 MPa
[0123]=1.23 MPa
13 23 33 43
Detection pressure of low-pressure sensor
(Ps)
×1 MPa
14 24 34 44 Suction Temperature (TS) ×1 °C
[0024]=24 °C
15 25 35 45 Coil Temperature 1 (TE) ×1 °C
16 26 36 46 Liquid Temperature (TL) ×1 °C
17 27 37 47 Outdoor Temperature (TO) ×1 °C
18 28 38 48 Low-pressure saturation temperature (TU) ×1 °C
19 29 39 49 Current of compressor 1 (I1) ×1 A
[0135]=13.5 A
1A 2A 3A 4A Current of compressor 2 (I2) ×1 A
1B 2B 3B 4B PMV1 + 2 ×1 pls [0050]=500 pls
1C 2C 3C 4C PMV3 ×1 pls [0050]=500 pls
1D 2D 3D 4D Compressor 1, 2 ON/OFF *2
1E 2E 3E 4E Outdoor fan mode ×1 [0031]=Mode 31
1F 2F 3F 4F Horse power of outdoor unit ×1 HP [0016]=16HP

Содержание