KAW-МЕТ P10 [20/52] Ventilation important information

KAW-МЕТ P10 [20/52] Ventilation important information
20
NOTE: You can not connect more than one device to the flue gases outlet.
Properly constructed flue pipe should be made of thermally conductive material slightly so
that it can stay warm. It has to be tight. If, in order to connect the furnace is not performed
tubing must perform the initial pressure test of walls. Flue pipe must have a minimum cross
section of 6.25 dm ² (eg. 25 cm x 25 cm). The section must be constant. It may not have
more than two slopes, the slope angle with the vertical shall not exceed 45 ° to the flue of up
to 5m. And 20 ° for tubes of bigger heights. The chimney draft at the base of the chimney
must be 5 to 10 Pa, in most cases it requires a suitable controller mounted within.
Note
The controller must be visible and easily accessible from the room where the fireplace is
located, it must be closed in the same time reducing the draft (and adjusted depending on
the outside air in the hood). Pay attention to the condition of the existing flue, many of
which are obsolete or are inadequate, they may also be subject to fast or too dirty, which is
seen most often can not withstand the high temperatures that reach the smoke. To avoid
any risk, we recommend you put the pipe in the exhaust pipe (brick) along its entire height.
Too large a cross-section of the flue may be too much space to heat which in turn can cause
interference to the furnace, in order to avoid them we recommend that this type of casing
pipe along its entire height.
We are not responsible for the installations comply with standards or recommendations
contained herein or for systems in which they are used more inappropriate materials.
8. Ventilation important information
Do not overheat the device.
Do not fire up at a time when in the room are flammable gases.
With the unit at the time of firing, there may be smoke if you installed a ventilation
system creates a vacuum in the room where the appliance is located, this applies to
most rooms equipped with a mechanical extraction system VMC (such as the kitchen,
etc..).
Ensure that the air required for burning can be taken in sufficient quantities from the
room where the stove is installed. If the structure of the building is such that the
amount of air is too small to provide oxidation and ventilation should be provided for
the installation of additional air supply.
9. Maintenance Policies
Ash removing
The ash must be removed when it is necessary. Excessive ash prevents the circulation of air
necessary for burning. Ashes should be place into a metal container equipped with a tight