Connection to the chimney must be made with a pipe at least 150mm, 180mm or 200mm in diameter, depending on replace
type. The stub pipe connection and all other connections to the chimney need to be sealed tight. A special heat resistant paste or
heat resistant modelling glue need to be used here. It is recommended to set the angle of the connecting elbow to be no more than
45° (this prevents excess soot buildup in the connector) and to add a revision door in it (see connection design). Fireplace inserts
with stub pipes less than or equal to 200mm require a minimum chimney surface of 4 dm² (like. 20 cm x 20 cm). Its diameter must
be consistent on its entire length. A too big diameter can be too hard to heat and can lead to disruptions in stove functionality.
The chimney cannot have more than two slopes, and their angles cannot exceed 45° for chimneys up to 5m tall and 20° for taller
chimneys. One should check the condition of the existing chimney if there is going to be a replace connected to it. Many are leaky,
porous (get dirty fast) or not temperature resistant enough. To eliminate any risks, a certied steel insert ought to be inserted on
the entire length of the chimney.
The chimney draft at the base of the chimney must be 10 to 15 Pa, in most cases it requires a suitable controller mounted
within.




Chimneys should be located in the walls between the heated rooms. When the chimney is located in the wall of the building,
perform the isolation of a material resistant to high temperatures. Its absence may result in lowering the temperature of the
exhaust gases and loss the ue draft. Diameter of the ue should not be less than the diameter of duct into the chimney. If the ue
outlet exhaust gas damper is installed, it is in the closed position it should have a section which is not obscured by at least 25% of
the diameter of the exhaust duct. Chimneys should be installed above the roof in accordance with the applicable standard.

•  at roofs with a slope of roof slopes of less than 12 °, regardless of the roof structure, vents should be located at least 0.6 m
above the level of the ridge or edge of the building with sunken roofs
•  the steep roofs with a slope roofs over 12 ° and coverage:
◊  the easily inamed, ue outlets should be at least 0.6 meters above the level of the ridge
◊  a non-combustible, non-inammatory and inammatory dicult, outlet pipe should be at least 0.3 m from the
surface of the roof and in the distance measured in the horizontal direction of the surface of at least 1.0 m
•  The location of the chimney of the building next to the item causing an obstruction for the proper functioning of chimney,
the outlet should be in addition:
◊  over the plane of derived for 12 ° down to the level of the highest obstacles for chimneys located at a distance of 3
to 10 meters from the obstacle with steep roofs
◊  at least at the upper edge of the obstacles for chimneys located at a distance of 1.5 to 3.0 m from the obstacle of
◊  at least 0.3 m above the top of the obstacles for chimneys located at a distance of 1.5 m from the obstacle
fresh air intake
If the air supply is insucient to housing such as apartments equipped with mechanical ventilation must take additional fresh
air supply to the re from the outside or in the basement, if it is not heated in the winter. Diameter of air intake should be at least
¼ of the diameter of ue.

Installation and commissioning of the replace should be done by a qualied assembly team. Set on the foundation of
a replace should be level and then make the connections for central heating and ue. Then proceed with the installation of
accessories. Flue outlet must be connected to the chimney using a steel pipe, which must be mounted on the ue and put in the
chimney.
Filling of water in the heating system should be made not less than 1 m from re place insert on the return water pipe.
To make a hood is recommended to use heat-resistant panels reinforced with glass bber with a minimum thickness 20
mm. The interior of the hood should be put mineral wool with aluminium with a minimum thickness 25 mm coating inward the
replace. Within minimum 30 cm from the ceiling make horizontal deector that directs the heat generated by the furnace into
grilles mounted below the deector. Ventilation should be at least 30 cm from the ceiling. Air grilles should be designed in the way
that prevents clogging.

2


Design of the housing shall allow cleaning of the replace and the tting (pipe that connects replace to the chimney). Make
sure that tting’s elbow has cleaning hole included. The interior of the housing in the lower part to bring air from the room to keep
!
!