Airwell Rooftech 100 [11/62] Caution

Airwell Rooftech 100 [11/62] Caution
9
CLEARANCE
1. It must be high enough above the roof or ground to permit snow allowance and good drainage of
water with siphon
2. Keep duct connections outside the building to a minimum to reduce energy losses.
3. In addition to the service clearances noted above it is essential that provision is made for adequate
and safe service access to the appliance.
UNIT LOCATION
The drawing below illustrates the minimum service clearances to be provided around the unit to guarantee access
and proper operation. Take particular care
not to obstruct the outdoor coil in order to
ensure proper air circulation through the
appliance.
In addition to the service clearances stated
on the dimensions sheet, it is imperative that
safe and appropriate access to the unit is
provided for repairs and servicing.
* Removable condensates tray.
A
A
A
B
C
Models 100 120 140 160
A mm 1500 1500 1500 1500
B* mm 1800 1800 1800 1800
C mm 3000 3000 3000 3000
CAUTION
For Heatpump models, where the outdoor temperature is likely to fall
below +1°C, provide a system to prevent the siphon from freezing
(e.g. heating cord).
CONDENSATE DRAIN PAN
H
Relationship with available
outdoor pressure
The installer must imperatively supply a siphon.
1082
218
DIMENSIONS
FOR THE BASE MODULE
Ø 30
L = 30mm
Siphon to be supplied by
others