8
CONDENSATE DRAIN LINE
CABINET REMOVAL
When removing cabinet do not pull or lift it up by the discharge grilles, to avoid
any damages on articulated fasteners of the access doors.
After installing the unit, be sure that there is no more longitudinal and transversal
counterslopes avoiding condensate evacuation.
For that, use a square and spirit level to make sure that fan coil unit is level and that it is at a 90 degree angle
between the wall and floor (see fluorescent sticker on unit chassis).
Note : If the floor and the wall are not at right angle, it may be necessary to shim the fan coil unit to insure proper
installation. Manufacturer will not accept any responsability on units not being on proper level.
Each fan coil unit is supplied with a 16 mm ID condensate S-shaped pipe. The drain pipe extends approximately
60 mm out of the piping compartment, to ensure either floor or wall connection to the main drain piping.
For the special case of a horizontal encased
AHC unit, you must follow the connections as shown below:
On the AWC and AHC models, to hang the unit to the wall, it is necessary to remove the cabinet.
To achieve this:
Remove the fastener screws from the access hatch situated at the right end of the
unit, on the electrical connections side.
Withdraw the four screws that hold the casing attached to the two chassis
flanks.
Then, lift the casing vertically by pulling its forwards. Place it
carefully to one side.