Airwell AQCL 120 [13/20] Models 100 1200 130

Airwell AQCL 120 [13/20] Models 100 1200 130
Page 13
0
20
40
60
80
100
120
140
160
180
200
2
130
120
100
3 4
5
6
7 8
9
10 11
Models 100, 1200 & 130
Hydraulic Pump External Static Pressure (continued)
l/s
kPa
WATER FLOW (l/s) MODEL 100 MODEL 120 MODEL 130
Nominal (1) 4.74 5.44 5.97
Minimum (2) 3.16 3.63 3.98
Maximum (3) 7.90 9.07 9.95
(1) Eurovent conditions, Water : 12/7 °C, Air : 35 °C.
(2) With water ∆T : 7.5 K at nominal capacity.
(3) With water ∆T : 3 K at nominal capacity.