Chillers ULTIMA COMPACT
Chillers
Installation & Maintenance : 903-129 IM E 10/04/
C
19
Installation Data
WATER SYSTEM
UCC30SQ-1/1
UCC30DQ-1/1
UCC40SQ-1/1
UCC40DQ-1/1
UCC50SQ-2/1
UCC50DQ-2/1
UCC60SQ-2/1
UCC60DQ-2/1
UCC70SQ-2/1
UCC70DQ-2/1
UCC80SQ-2/1
UCC80DQ-2/1
Connections
Water Inlet / Outlet Female BSP in 1 1/2 1 1/2 2 2 2 2
Water Drain/Bleed in 1/2 1/2 1/2 1/2 1/2 1/2
Water System
Min. System Water Volume (2) l 308 411 514 493 719 822
Max. System Press Bar 10 10 10 10 10 10
OPTIONAL EXTRAS - ALL MODELS
Water Pump (3) In Line Pump
Nom External Head Std Single / R&S kPa 145 121 133 113 131 115
Nom External Head Larger Single/R&S kPa 189 147 235 215 188 169
Nom External Head Standard Twin kPa 145 135 131 121 116 107
Nom External Head Larger Twin kPa 195 185 180 170 164 155
Expansion Tank (4)
Water Capacity l 35 35 35 35 35 35
Buffer Tank
Max. Water Capacity (5) l 250 250 250 250 250 250
Pressurisation Unit
Water Inlet Connection in 1/2 1/2 1/2 1/2 1/2 1/2
UCC75D-2/1 UCC100D-2/1 UCC110D-4/2 UCC125D-3/1 UCC130D-4/2 UCC150D-3/1
Connections
Water Inlet / Outlet (1) DN65 DN65 DN80 DN65 DN80 DN65
Water Drain/Bleed In 1/2 1/2 1/2 1/2 1/2 1/2
Water System
Min. System Water Volume (2) l 399 519 533 453 460 800
Max. System Press Bar 10 10 10 10 10 10
OPTIONAL EXTRAS - ALL MODELS
Water Pump (3) In Line Pump
Nom External Head Std Single / R&S kPa 125 115 110 100 100 155
Nom External Head Larger Single/R&S kPa 200 190 160 170 150 200
Nom External Head Standard Twin kPa 105 155 115 150 100 140
Nom External Head Larger Twin kPa 135 130 165 205 150 200
Expansion Tank (4)
Water Capacity l 50 50 50 50 50 50
Buffer Tank
Max. Water Capacity - D l 250 250 250 420 250 420
Max. Water Capacity - SQ/DQ l 250 420 250 420 250 420
Max. Water Capacity - SSQ/DSQ l 250 420 250 420 250 420
Pressurisation Unit
Water Inlet Connection in 1/2 1/2 1/2 1/2 1/2 1/2
(1) Flanged to PN16.
(2) For minimum system volume refer to the Technical Manual.
(3) Nominal Cooling Duties based on 12/7°C water temperature and 30°C ambient, where output is the chilled water duty and input is the compressor input power.
(4) Expansion vessel may require reselecting for glycol and system volume, please refer to Airedale
(5) UCC30 and UCC40 dimensions change to 1450 x 2500 x 1310 when Buffer Tank fitted.