Delta Electronics DPB01N-P [5/9] Initial setting

Delta Electronics DPB10N-P [5/9] Initial setting
- 5 -
Quick Setup Mode Advanced Setup Mode Measuring Mode
Set up N.O./N.C. of OUT1 and
OUT2
Press
Set up hysteresis
Press
SV of OUT1
(Set OUT1 to easy mode)
Press
Set up output response time
Press
Set up power saving mode
Press
Set up upper limit of OUT2
(Set OUT2 to hysteresis mode / window
mode)
Press
Set up PV display color
Press
Set up switching color referencing
output items
Press
Set up lower limit of OUT2
(Set OUT2 to hysteresis mode / window
mode)
Press
Set up unit
Press
Return to “set up OUT1 mode”
Set up code
Press
SV of OUT2
(Set OUT2 to easy mode)
Press
Returning to output setting
Set up copy function
Press
Set up analog output switch
Press
Return to default settings
Press
Return to “set up auxiliary
display”
Initial Setting
1. Units: DPA provides many units for users, including kPa, kgf/cm
2
, bar, psi, mmHg and inchHg. In the easy mode, you can press and
find
to set the unit to the desired one.
2. Output status: You can set up 2 output status in DPA, N.O. (normally open) and N.C. (normally closed). In the easy mode, you can press
and fine to set up the output status for OUT1 and OUT2.
3. Response time: Referring to the time required for the pressure to reach output status. For example, “50” refers to once the pressure has
reached the output status, it has to last for 50ms before the output starts to operate. In the easy mode, press
and find .
Use
to set up the response time.
Output Mode Setting
There are 3 output modes in DPA: Easy, Hysteresis and Window
1. Easy Mode: Set up pressure P. When the pressure measured is bigger than (P + dP), the output will be ON. When the pressure measured
is smaller than P, the output will be OFF. (See Figure 1: Output in Easy Mode)
In the “Measuring Mode”, press
and find (OUT1) and (OUT2). Use to set up P value.
In the “Advanced Setup Mode”, press
and find . Use to set up “dP” value.
[Figure 1: Output in Easy Mode]