Fluke 1745 [41/72] Signal sampling

Fluke 1745 [41/72] Signal sampling
Power Quality Logger
Using the 1745 Power Quality Logger
27
Signal Sampling
Input signals (up to three voltages and four currents) are filtered with an anti-
aliasing filter and digitized with a 16-bit A/D converter. The sampling rate is
10.24 kHz. All parameters are calculated from this data.
Resolution Accuracy
Resolution and accuracy depend on the logging parameter. For details see
“Technical Specifications”.
Voltage Variations
The interval value of the voltage is defined as the mean value of the RMS
values over the interval length defined in PQ Log.