Fluke 1745 [58/72] Maximum number of intervals for logging funtion p

Fluke 1745 [58/72] Maximum number of intervals for logging funtion p
1745
Users Manual
44
Maximum Number of Intervals for Logging Funtion P
The maximum recording period can be calculated by multiplying the interval
time defined in PQ Log with the maximum number of intervals in the
following table.
Version P, V+I A, V+I
Averaged periods > 24,000 > 10,000
General Information
Intrinsic uncertainty Valid for reference conditions, and guaranteed for
two years.
Quality system Developed, designed, and manufactured according to
DIN ISO 9001.
Recalibration interval Fluke recommends a recalibration interval of no
more than two years, depending on use.
Reference conditions 23 C ±2 K, 230 V ±10 %
50 Hz ± 0.1 Hz / 60 Hz ± 0.1 Hz
Phase sequence: L1 or A, L2 or B, L3 or C
Interval length: 10 minutes, 3-phase Wye
configuration.
Power supply: 88 to 265 V AC