Galletti LEW CS/CL 244 [39/56] Technical data of optional hydronic modules

Galletti LEW CS/CL 062 [39/56] Technical data of optional hydronic modules
Page39of56
RG66006951Rev.01
3 Technicaldataofoptionalhydronicmodules
Hydronicmodules,recommendedasanoptionalfeatureforLEWunits,bringtogether,injustasingle,compactand
silentsolution,themaincomponentsoftheprimarycircuitofthehydraulicsystemservedbyLEWmachines.Each
hydraulicmodulecontainsbothcircuits:
ON/OFFhydraulicpump
Bladetypeflowswitchtopr
eventicefromforming,whichiscausedbytheevaporationoftherefrigerantinthe
plateheatexchanger.(LEWCDunitshaveaflowswitchontheutilityside,LEWWHunitshaveaflowswitch
bothontheutilityandthesourceside)
Expansionvesseltomanagechangesinvolumeaffecti
ngtheamountofwatercontainedintheLEWunitand
themoduleitself
Safetyvalve(setto3barasstandard)
Themodulehasitsownelectricpanel,whichpowersthepumps,protectsthemwithmotoroverloadprotectionsand
receivestheconsentfromtheLEWunits.ThepowerisnotsuppliedbytheLEWun
it,butdirectlybytheexternalline.
Themoduleisinsulatedtoreducethesoundemissionsofthepumps.


3.1 Characteristic curves of the hydraulic pumps associated to the units
Thegraphicsdisplayedinthisparagraphshowtheusefulhead(netwiththeinternallossesoftheunits)oftheHP
pumpsandLPpumpsintheoptionalhydronicmodule.
AtthenominalflowrateslistedinthischapterinTablesIandII,thelowpressureLPpumpsprovide60kPaofuse
ful
headontheutilitysideand70kPaonthedissipationside.ThehighpressureHPpumpsprovideausefulheadequalto
140kPaforbothhydrauliccircuits.
UsefulheadforLEW041,042pumpsonutilityside UsefulheadforLEW051,052pumpsonutilityside
UsefulheadforLEW061,062,071,072pumpsonutilityside UsefulheadforLEW081,082pumpsonutilityside

Содержание