Yaskawa CIMR-UU2A0042A [178/644] Pid feedback input methods

Yaskawa CIMR-UU2A0068A [178/644] Pid feedback input methods
Table 5.9 PID Setpoint Sources
PID Setpoint Source Settings
Analog Input A1 Set H3-02 = C
Analog Input A2 Set H3-10 = C
Analog Input A3 Set H3-06 = C
MEMOBUS/Modbus Register 0006 H Set bit 1 in register 000F H to 1 and input the setpoint to register 0006 H
Pulse Input RP Set H6-01 = 2
Parameter b5-19 Set parameter b5-18 = 1 and input the PID setpoint to b5-19
Note: A duplicate allocation of the PID setpoint input will cause an oPE alarm.
n
PID Feedback Input Methods
Input
one feedback
signal for normal PID control or input two feedback signals can for controlling a differential process value.
Normal PID Feedback
Input the PID feedback signal from one of the sources listed in Table 5.10:
Table 5.10 PID Feedback Sources
PID Feedback Source Settings
Analog Input A1 Set H3-02 = B
Analog Input A2 Set H3-10 = B
Analog Input A3 Set H3-06 = B
Pulse Input RP Set H6-01 = 1
Note: A duplicate allocation of the PID feedback input will cause an oPE alarm.
Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed in Table 5.11. The differential
feedback function is automatically enabled when a differential feedback input is assigned.
Table 5.11 PID Differential Feedback Sources
PID Differential Feedback Source Settings
Analog Input A1 Set H3-02 = 16
Analog Input A2 Set H3-10 = 16
Analog Input A3 Set H3-06 = 16
Note: A duplicate allocation of the PID differential feedback input will cause an oPE alarm.
5.2 b: Application
178
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual