Yaskawa CIMR-UU2A0042A [518/644] T3 asr and inertia tuning

Yaskawa CIMR-UU4A0240A [518/644] T3 asr and inertia tuning
No.
(Addr.
Hex)
Name LCD Display Description Values Page
T2-15
(0756)
Pull-In Current Level for
PM Motor Tuning
Pull-In I Lvl
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
OLV/PM AOLV/PM CLV/PMOLV/PM AOLV/PM CLV/PM
Sets the amount of pull-in current to use for Auto-Tuning as a
percentage of the motor rated current. Increase this setting for
high inertia loads.
Default: 30%
Min.: 0
Max.: 120
142
T2-16
(0738)
PG Number of Pulses
Per Revolution for PM
Motor Tuning
PG Pulses/Rev
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
Sets the number of pulses per revolution for the PG being used
(pulse generator or encoder).
Default: 1024
ppr
Min.: 1
Max.: 15000
142
T2-17
(0757)
Encoder Z-Pulse Offset
(Δθ)
Z-Pulse Offset
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
CLV/PM
Sets the offset between encoder offset and the rotor magnetic axis.
Default: 0.0 deg
Min.: -180.0
Max.: 180.0
142
<1> The availability of certain Auto-Tuning methods is determined by the control mode selected for the drive.
<2> The setting range is determined by parameter A1-02, Control Method Selection.
<3> Default setting is determined by parameters A1-02, Control Method Selection, and o2-04, Drive Model Selection.
<4>
Default setting is determined by parameter o2-04, Drive Model Selection.
<5> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<6> Default setting is determined by parameter T2-02, PM Motor Code Selection, and the drive capacity.
u
T3: ASR and Inertia Tuning
No.
(Addr.
Hex)
Name LCD Display Description Values Page
T3-01
(0760)
Inertia Tuning
Frequency Reference
Test Signal Freq
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Sets the frequency of the test signal used during Inertia Tuning
and ASR Gain Auto-Tuning. Reduce this value if the inertia is
large or if a fault occurs.
Default: 3.0 Hz
Min.: 0.1
Max.: 20.0
143
T3-02
(0761)
Inertia Tuning
Reference Amplitude
Test Signal Ampl
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Sets the amplitude of the test signal used during Inertia and ASR
Gain Auto-Tuning. Reduce this value if the inertia is too large or
if a fault occurs.
Default: 0.5 rad
Min.: 0.1
Max.: 10.0
143
T3-03
(0762)
Motor Inertia Motor Inertia
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Sets the motor inertia. Default setting is the inertia of a Yaskawa
motor.
Default:
<2>
<3>
Min.: 0.0001
kgm
2
Max.: 600.00
kgm
2
143
T3-04
(0763)
<1>
ASR Response
Frequency
System Resp Freq
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Sets the response frequency of the mechanical system connected
to the motor. Oscillation may result if set too high.
Default: 10.0 Hz
Min.: 0.1
Max.: 50.0
143
<1> Displayed only when performing Inertia Tuning or ASR Gain Auto-Tuning (T1-01 = 8 or T2-01 = 9).
<2> Default setting is determined by parameter E5-01, Motor Code Selection.
<3> Default setting is determined by parameters C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.
B.14 T: Motor Tuning
518
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual

Содержание