ELECTRICAL SPECIFICATIONS
EWAD C
-
XR
C22
MODEL
POWER SUPPLY
Phases
Nr
3
Frequency
Hz
50
Voltage
V
400
Voltage tolerance Minimum
%
-
10%
Voltage tolerance Maximum
%
+10%
UNIT
Maximum starting current
A
1458
Nominal running current cooling
A
1136
Mximum running current
A
1431
Maximum current for wires
sizing
A
1566
FANS
Nominal running current cooling
A 78
COMPRESSORS
Phases
Nr
3
Voltage
V
400
Voltage tolerance Minimum
%
-
10%
Voltage tolerance Maximum
%
+10%
Maximum running current
A
451
451
451
Starting method
---
Y
-
Fluid: Water
Allowed voltage
tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the compressor at 75% maximum load + fans current for the circuit at 75%.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.