Daikin EWAD830C-SS [49/96] Operating limits

Daikin EWADC11C-XS [49/96] Operating limits
49
Water content in cooling circuit
The cooled water distribution circuits should have minimum water content to avoid excessive compressors start and stop.
In fact, each time the compressor starts up, an excessive quantity of oil goes from the compressor sump and simultaneously there is
a rise in the temperature of the compressor motor’s stator due to the inrush current during the start-up.
To prevent damage to the compressors, It has been envisaged the application of a device to limit frequent stops and restarts.
During the span of one hour there will be no more than 6 starts of the compressor. The plant side should therefore ensure that the
overall water content allows a more constant functioning of the unit and consequently greater environmental comfort.
The minimum water content per unit should be calculated using this simplified formula:
For 2 compressors unit
M (liters) = ( 0.1595 x ∆T(°C) + 3.0825 ) x P(kW)
For 3 compressors unit
M (liters) = (0.0443 x ∆T(°C) + 1.6202) x P(kW)
where:
M minimum water content per unit expressed in litres
P Cooling Capacity of the unit expressed in kW
∆T evaporator entering / leaving water temperature difference expressed in °C
This formula is valid for:
- standard microprocessor parameters
For more accurate determination of quantity of water, it is advisable to contact the designer of the plant.
OPERATING LIMITS
-30
-20
-10
0
10
20
30
40
50
60
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16
Condenser Inlet Air Temp. (°C)
Evaporator Leaving Water Temp. (°C)
Operation with Glycol
(below 4°C Evap LWT)
Fan Speed Regulation required
(below 10°C Amb. Temp)
Speedtroll required (below -10°C Amb. Temp)
Standard Efficiency High Efficiency Premium Efficiency