Daikin EWAPC11AJYNN [18/41] Specifications

Daikin EWAPC10AJYNN [18/41] Specifications
Chillers • R-407C • EWAP-AJYNN
1
3
Hydronic Systems • Chillers
18
3 Specifications
3-2 ELECTRICAL SPECIFICATIONS EWAP800AJYNN EWAP900AJYNN EWAP950AJYNN EWAPC10AJYNN EWAPC11AJYNN EWAPC12AJYNN
Power Supply Name YN
Phase 333333
Frequency Hz 50 50 50 50 50 50
Voltage V 400 400 400 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Unit Starting Current A 1050 1054 1116 1120 1165 1265
Nominal Running Current
Cooling
A 517 561 673 729 780 796
Maximum Running Current A 647 703 767 833 896 963
Max unit current for wires
sizing
A 668 728 788 848 908 1002
FanPhase 333333
Voltage V 400 400 400 400 400 400
Nominal Running Current
Cooling
A485256606472
CompressorPhase 333333
Voltage V 400 400 400 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Maximum Running Current A 599 651 711 773 832 891
Starting Method Star-delta
Notes Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Max unit starting current: Starting current of biggest compressor + 75% of nominal absorbed current of the other
compressor + fans current.
Max unit current for wires sizing : compressor FLA (Full Load Ampere) + fans current.
3-2 ELECTRICAL SPECIFICATIONS EWAPC13AJYNN EWAPC14AJYNN EWAPC15AJYNN EWAPC16AJYNN EWAPC17AJYNN EWAPC18AJYNN
Power Supply Name YN
Phase 333333
Frequency Hz 50 50 50 50 50 50
Voltage V 400 400 400 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Unit Starting Current A 1248 1344 1402 1405 1489 1491
Nominal Running Current
Cooling
A 823 864 1012 1070 1122 1173
Maximum Running Current A 1026 1082 1152 1222 1285 1347
Max unit current for wires
sizing
A 1062 1122 1186 1242 1302 1362
FanPhase 333333
Voltage V 400 400 400 400 400 400
Nominal Running Current
Cooling
A768088889296
CompressorPhase 333333
Voltage V 400 400 400 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Maximum Running Current A 950 1002 1064 1134 1193 1251
Starting Method Star-delta
Notes Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Max unit starting current: Starting current of biggest compressor + 75% of nominal absorbed current of the other
compressor + fans current.
Max unit current for wires sizing : compressor FLA (Full Load Ampere) + fans current.