Daikin EWLP040KAW1N [103/138] Replacing the controller

Daikin EWLP040KAW1N [103/138] Replacing the controller
Troubleshooting ESIE03-03
3–22 Part 3 – Troubleshooting
3
1
3
4
5
4.5 Replacing the Controller
Replacing the
controller
To replace the controller, proceed as follows:
Entering the factory
menu
The factory menu is used to set up the identification parameters of the unit according to its controller.
To enter the factory menu, proceed as follows:
For more information on the controller, see "The Digital Controller: EUW(L)5-24KZW1" on page 2–11.
Step Action
1 Remove the connections of the old controller.
2 Remove the old controller.
3 Install the new controller in the same way as the old controller.
4 Reconnect the controller.
5 Reprogram the controller.
Step Action Result
1 Turn ON the power supply.
Make sure that the unit is not working.
If it is, press cto switch OFF the
unit.
2
Press
sand psimultaneously for
5s.
After 5 s, 0 lights up.
3
Scroll using
uor dto go to 177.
4
Press
s.
You have entered the factory menu. The screen
displays /3.
If... Then...
There is no controller
installed
E1, E2 or E3 appears
on the screen.
The controller is
installed and correctly
wired
The temperature of
sensor 1 appears.