Low SH protections This screen allows you to set the low superheat protection settings.
LOP protection This screen allows you to set the LOP protection parameters.
MOP protection These screens allow you to set the MOP protection parameters
P Low Limit : Setpoint of the low limit function
P Int. Time : Integral time used for the low limit function
EXV Settings
Low SHeat Protection
Low Limit –1.0 ˚C
Int. Time 01.0 ˚C
P LOP Limit : Setpoint of the LOP protection function
P Int. time : Integral time used for the LOP function
EXV Settings
LOP Protection
LOP Limit – 30.0 ˚C
Int. Time 04.0 ˚C
P MOP Limit : Setpoint of the MOP protection function
P Int. Time : Integral time used for the MOP function
P Start-Up Delay : Start-up delay of the MOP functions at start-up
EXV Settings
MOP Protection
MOP Limit 12.0 ˚C
Int. Time 04.0 ˚C
EXV Settings
MOP Protection
Start-Up Delay 090 s