Outdoor ambient
temperature reset
The OAT mode can be used to modify the setpoint in function of the ambient temperature. The user is
able to choose to use the OAT mode or not. The result of using the ambient mode is that the unit will
be used more efficiently and that the modified setpoint will be displayed under the normal setpoint.
The OAT setpoint parameters and function can be set in the user menu.
This function is only available when the optional pCOe (expansion board) is present. This is because
the ambient sensor is connected to this pCOe.
Function
description
P Above 35°C Ambient Temperature, there is no reset. The unit will operate with the local or dual
setpoint.
P Between 27°C and 35°C Ambient Temperature, the unit will change the actual setpoint according
to the offset.
P Below 27°C Ambient Temperature, the unit will operate with actual setpoint equal to the local or
dual setpoint + setpoint diff.
Lvg Water Temp
Setpoint Reset
4-20mA
chLWT Setpoint
Override Limits
Setp. Diff.
03.0 ˚C
Ambient Temp.
Setpoint
diff. (3 )
Local or Dual
Setpoint
Actual Setpoint
Max Reset
(27 C)
No Reset
(35 C)
Setpoint Diff.
OAT chWT Reset
Max Reset
No Reset
3 ˚C
27 ˚C
35 ˚C