ESIE07-04 The Digital Controller
Part 2 – Functional Description 2–67
3
2
4
5
1
Expansion board
probe screen
This screen allows you to enable or disable the analog input (from the expansion board).
This screen is only visible when the unit has an expansion board (units /A and /Z). The ambient sensor
which can be connected to the expansion board analog input B1 is used for setpoint reset OAT. This
sensor is not standard (SPN unit).
Controller probes
offset
These screens allow you to set the offset of the analog inputs.
Time to down load
compressor
This screen allows you to set the time to down load compressor before the pump down procedure
starts.
Reload and
re-unload comp
This screen allows you to set the reload and re-unload T.
P B1 : Y : Analog input is enabled
P B1 : N : Analog input is disabled
P B1 Offs : Offset of sensor B1, adjust if needed
EXP Probes enable
B1 : Y
EXP Probes Offs
B1 Offs : 00.0 ˚C
Inputs Probes Offset
B1 : 0.0 B2 : 0.0
B4 : 0.0 B5 : 0.0
Input Probes Offset
B6 : 0.0 B7 : 0.0
B9 : 0.0 B10 : 0.0
Time to Download Compressor
30 s
P DT : T above and below setpoint to reload or re-unload compressor
DT to Reload and Re-unload Comp
0.7 ˚C