Daikin EUWAC5FBZW1 [25/28] Fan characteristics

Daikin EUWAC5FBZW1 [25/28] Fan characteristics
EUWAC5~10FBZW1
Packaged air-cooled water chillers
4PW61657-1 – 07.2010
Installation and operation manual
22
ANNEX III
Fan characteristics
The figures below represent the external static pressure of the unit (ESP) in function of the air flow of the fans (AF).
EUWAC5FBZW1
Values are applicable only in case the fanspeed controller is not
actived.
EUWAC8FBZW1
Values are applicable only in case the head pressure switch for
fanspeed control is not actived.
EUWAC10FBZW1
Values are applicable only in case the head pressure switch for
fanspeed control is not actived.
ESP External static pressure
AF Air flow
ESP External static pressure
AF Air flow
1 ESP with pulley closed (factory setting)
2 ESP with pulley 1 turn open
3 ESP with pulley 2 turns open
4 ESP with pulley 3 turns open
5 ESP with pulley 4 turns open
110
100
90
80
70
60
50
40
30
20
10
0
ESP
(Pa)
1.00 1.05 1.10 1.15 1.20 1.25 1.30
AF
(m
3
/sec)
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
ESP
(Pa)
1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
AF
(m
3
/sec)
12345
ESP External static pressure
AF Air flow
1 ESP with pulley closed (factory setting)
2 ESP with pulley 1 turn open
3 ESP with pulley 2 turns open
4 ESP with pulley 3 turns open
5 ESP with pulley 4 turns open
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
ESP
(Pa)
1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5
AF
(m
3
/sec)
12345
4PW61657-1_digital_EN.book Page 22 Friday, August 27, 2010 8:09 AM