Daikin ER60MZY [7/14] Capacity tables

Daikin ER60MZY [7/14] Capacity tables
3
Capacity tables
3-1
Cooling capacities for air conditioning applications
AMBIENT TEMPERATURE
(°C)
15 20 25 30 35 40 43
SDP (°C)
MODEL
CC PI CC PI CC PI CC PI CC PI CC PI CC PI
2
40 124 28.4 118 32.1 112 35.4 106 38.4 99.4 41.0 93.2 43.4 89.5 44.6
50 164 37.4 156 40.9 148 44.3 140 47.6 132 50.8 124 53.9 119 55.6
60 191 44.2 182 48.2 172 52.6 162 57.4 152 62.7 143 68.5 137 72.1
5
40 140 29.5 133 33.2 127 36.5 120 39.5 114 42.1 107 44.4 103 45.7
50 182 38.9 174 42.5 166 45.9 158 49.2 150 52.4 142 55.4 137 57.2
60 211 46.6 201 50.6 191 55.0 181 59.9 171 65.2 161 70.9 155 74.6
8
40 155 30.6 148 34.3 142 37.6 135 40.5 128 43.2 121 45.5 117 46.8
50 200 40.5 192 44.1 184 47.5 177 50.8 169 54.0 161 57.0 156 58.8
60 231 49.1 221 53.1 210 57.5 200 62.4 190 67.6 179 73.4 173 77.0
11
40 171 31.7 164 35.3 157 38.7 149 41.6 142 44.3 135 46.6 131 47.8
50 219 42.1 211 45.7 203 49.1 195 52.4 187 55.6 179 58.6 174 60.4
60 251 51.5 240 55.5 230 60.0 219 64.8 208 70.1 148 56.9 144 59.6
14
40 186 32.8 179 36.4 171 39.7 164 42.7 157 45.4 149 47.7
Out of operating range
50 237 43.7 229 47.2 221 50.7 213 54.0 205 57.1 198 60.2
60 270 54.0 259 58.0 249 62.4 238 67.3 227 72.6 162 58.7
3TW54372-1
SYMBOLS
CC : Cooling capacity (kW)
PI : Total power input = compressor + fans + control circuit (kW)
SDP : Suction dew point
NOTES
Conditions according EN13215
Superheat = 10°C
Subcool = 5°C
Remote evaporator R-407C ER40-60MZY
3
3-1
5
Condensing Units
Скачать