Daikin EWWD800I-SS [47/51] Specification text

Daikin EWWD800I-SS [47/51] Specification text
3
1
10
Hydronic Systems • Single Unit
47
Single Unit • Water cooled chiller, standard efficiency • EWWD-I-SS
10 Specification text
10 - 1 Specification Text
SPC_1-2-3_Rev.00_1
Technical Specifi cation for Water Cooled Screw Chiller
GENERAL
The water cooled screw chiller will be designed and manufactured in accordance with following European directives:
Construction of pressure vessel 97/23/EC (PED)
Machinery Directive 2006/42/EC
Low Voltage 2006/95/EC
Electromagnetic Compatibility 2004/108/EC
Electrical & Safety codes EN 60204–1 / EN 60335-2-40
Manufacturing Quality Stds UNI – EN ISO 9001:2004
The unit will be tested at full load in the factory at the nominal working conditions and water temperatures. Before shipment a
full test will be held to avoid any losses.
Chiller will be delivered to the job site completely assembled and charged with right refrigerant and oil quantity.
Comply with the manufacturer instructions for rigging and handling equipment.
The unit will be able to start up and operate as standard at full load and condenser entering fl uid temperature from .… °C to
.… °C with an evaporator leaving fl uid temperature between …. °C and …. °C.
All units published performances have to be certifi ed by Eurovent.
REFRIGERANT
Only R-134a will be accepted.
PERFORMANCE
3 Number of water cooled screw chiller: ...............
3 Cooling capacity for single water cooled screw chiller: ............... kW
3 Power input for single water cooled screw chiller in cooling mode: ............... kW
3 Shell & tube evaporator entering water temperature in cooling mode: ............... °C
3 Shell & tube evaporator leaving water temperature in cooling mode: ............... °C
3 Shell & tube evaporator water fl ow: ............... l/s
3 Shell & tube condenser entering water temperature in cooling mode: ............... °C
3 Shell & tube condenser leaving water temperature in cooling mode: ............... °C
3 Shell & tube condenser water fl ow: ............... l/s
3 The unit should work with electricity in range 400V ±10%, 3ph, 50Hz without neutral and shall only have one power
connection point.
UNIT DESCRIPTION
Chiller shall include as standard: 1, 2 or 3 independent refrigerant circuits, semi-hermetic rotary single screw compressors,
electronic expansion device (EEXV), refrigerant direct expansion shell & tube heat exchangers, R134a refrigerant, lubrication
system, motor starting components, control system and all components necessary for safe and stable unit operation.
Chiller will be factory assembled on a robust base-frame made of zinc coated steel, protected by an epoxy paint.
NOISE LEVEL AND VIBRATIONS
Sound pressure level at 1 meter distance in free fi eld, semispheric conditions, shall not exceed ………dB(A). The sound
pressure levels must be rated in accordance to ISO 3744.
Other types of rating unacceptable. Vibration level should not exceed 2 mm/s.
DIMENSIONS
Unit dimensions shall not exceed following indications:
3 unit length ............... mm,
3 unit width ............... mm,
3 unit height ............... mm.